2
|
Troubleshooting
Service manual
126
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
1
Check if the power supply is conform with the regulations. See
356].
Possible cause:
▪
Faulty or disturbance of the power supply (imbalance >10%),
▪
Power drop,
▪
Short circuit.
2
Perform a check of the inverter PCB A6P. See
274].
Possible cause:
Faulty inverter PCB A6P.
3
Perform a check of the compressor M2C. See
Possible cause:
Faulty compressor M2C.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.112 LC-01 – Transmission abnormality
Trigger
Effect
Reset
No transmission between
PCB boards.
Unit will stop operating.
Automatic reset.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB or wrong capacity setting.
2
Perform a check of the noise filter PCB. See
Possible cause:
Faulty noise filter PCB.
3
Perform a check of the inverter PCB. See
274].
Possible cause:
Faulty inverter PCB.
4
Perform a check of the fan inverter PCB. See
259].
Possible cause:
Faulty fan inverter PCB.
5
Check that the bridge connector X4A of the fan inverter PCB is correctly
connected. See
259].
Possible cause:
Open jumper X4A on fan inverter PCB.
6
Check the wiring between the PCB's. See
385].
Possible cause:
Faulty wiring between PCB's.
7
Check if the correct spare part is installed for all PCB's. See checking
procedures of the specific PCB's.
Possible cause:
Wrong spare part PCB installed.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.