2
|
Troubleshooting
Service manual
119
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
2.3.104 L5-03-05-07 – Output overcurrent detection on inverter PCB A3P
Main error code
Sub error code
Unit
L5
03
Main
05
Sub 1
07
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Inverter PCB A3P detects
overcurrent to power
transistor.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check if the power supply is conform with the regulations. See
Possible cause:
▪
Faulty or disturbance of the power supply (imbalance >10%),
▪
Power drop,
▪
Short circuit.
2
Check if the refrigerant circuit is clogged. See
Possible cause:
Clogged refrigerant circuit.
3
Check that all stop valves of the refrigerant circuit are open. See
Possible cause:
Closed stop valve in the refrigerant circuit.
4
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
363].
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
5
Perform a check of the inverter PCB A3P. See
Possible cause:
Faulty inverter PCB A3P.
6
Perform a check of the compressor M1C. See
221].
Possible cause:
Faulty compressor M1C.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.