2
|
Troubleshooting
Service manual
58
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
2
Perform
a
check
of
the
discharge
pipe
thermistor.
See
Possible cause:
Faulty discharge pipe thermistor or connector fault.
3
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
4
Check if the refrigerant circuit is correctly charged. See
363].
Possible cause:
Refrigerant shortage.
5
Perform a check of the compressor. See
Possible cause:
Faulty compressor.
6
Perform a check of the lower heat exchanger expansion valve. See
Possible cause:
Faulty lower heat exchanger expansion valve.
7
Perform a check of the upper heat exchanger expansion valve. See
Possible cause:
Faulty upper heat exchanger expansion valve.
8
Perform a check of the expansion valve(s) of the indoor unit(s). See service
manual of the respective indoor unit(s) for more information.
Possible cause:
Faulty indoor unit expansion valve.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.36 F3-20-21-22 – Compressor body temperature too high
Main error code
Sub error code
Unit
F3
20
Main
21
Sub 1
22
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Body temperature >safety
value certain times within
certain minutes, see
Unit will stop operating.
Manual reset via user
interface.
Automatic reset when
body temperature <reset
value, see
449].