3
|
Components
Service manual
308
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
3
Activate
Cooling
or
Heating
operation via the Cool/Heat master user
interface.
4
Check the functioning of the outdoor unit fan.
Outdoor unit fan …
Action
Rotates continuously (without
interruption)
DC fan motor assembly is OK. Return to
the troubleshooting of the specific error
and continue with the next procedure.
Does not rotate or rotates for a short
time
Continue with the next step.
5
Stop the unit operation via the central controller.
6
Turn OFF the respective circuit breaker.
DANGER: RISK OF ELECTROCUTION
Confirm the rectifier voltage is below 10 V DC before proceeding, see
7
Check that the DC fan motor connector X1A is properly connected to the PCB.
8
Unplug the DC fan motor connector and measure the resistance between the
pins 1–2, 1–3, and 2–3 of the DC fan motor connector.
Result:
All measurements MUST be 8.27 Ω±5% at 20°C.
INFORMATION
Winding resistance values above are given for reference. You should NOT be reading
a value in kΩ or a short‑circuit. Make sure that the propeller fan blade does NOT
rotate, as this could affect resistance measurements.
9
Measure the insulation resistance for the motor terminals. Measurements
between each phase and ground must be >1°MΩ.
Are the measured resistance values
correct?
Action
Yes
Perform a check of the fan inverter PCB,
see
No
Replace the DC fan motor, see
Problem solved?
After all checking procedures listed above have been performed:
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Repair procedures
To remove the propeller fan blade assembly
Prerequisite:
Stop the unit operation via the central controller.
Содержание VRV IV+