2
|
Troubleshooting
Service manual
116
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
4
Check (by touching) if refrigerant is flowing through the radiant cooling
refrigerant circuit. The radiant cooling refrigerant circuit should be warm if
refrigerant is flowing. If no refrigerant flow, perform a check of the liquid
cooling expansion valve, see
244].
Possible cause:
No refrigerant flow through the radiant cooling refrigerant
circuit.
5
Perform a check of the liquid cooling expansion valve. See
244].
Possible cause:
Faulty liquid cooling expansion valve.
6
Check ambient temperature. Check if outdoor unit location temperature
differs drastically.
7
Check if there is discharge air by-pass on installation location.
Possible cause:
External noise. Check further on how to eliminate external
factors.
8
Perform a check of the fan inverter PCB A4P. See
259].
Possible cause:
Faulty fan inverter PCB A4P.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.102 L4-07-19-21 – Fan inverter PCB A7P high fin temperature
Main error code
Sub error code
Unit
L4
07
Main
19
Sub 1
21
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Thermistor located inside
the power module of the
fan inverter PCB detects a
temperature higher than
a certain value.
Unit will stop operating.
Manual reset via remote
controller.
Outdoor unit power reset.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
Prerequisite:
Stop the unit operation via the central controller.
1
Turn OFF the respective circuit breaker.