The first line in the screen shows the progressive alarm number, the time and date on which the alarm was
recorded.
The second and the third lines in the screen show the alarm message.
The fourth line in the screen shows the ambient temperature and humidity at the time of alarm activation.
Ambient humidity is only displayed if the corresponding probe is enabled.
7.13 Summer/Winter menu
The Summer/Winter menu screen is designed to switch heat pump units from summer (cooling) to winter
(heating) mode.
Select the item “Summer/Winter” in the menu and click Enter to access the Summer/Winter menu: screen R0
appears on the display.
Unità in R0
- ESTATE -
ENTER per
- INVERNO -
Unit in R0
- SUMMER -
Press ENTER for
- WINTER -
Unid. en R0
- VERANO -
ENTER par
- INVIERNO -
A click on the Enter button changes the unit status. This is feasible on exclusive condition that the unit is turned
to OFF and automatic mode switching is not enabled in screen C6 of the Manufacturer menu.
Access to the R0 screen is not possible when mode switching is enabled using the digital input.
7.14 Unit Selection menu
The Unit Selection menu screen is designed to select the displayed unit when several units are connected
through a local p-LAN network. This operation is feasible from the display having network address 32.
Select the item “Unit Selection” in the menu and click Enter to access the Unit Selection menu: screen L0
appears on the display.
Unità n. 01 L0
ENTER
per cambiare unità
controllata
Present unit n.01 L0
Press ENTER to
change controlled
unit
Unid. N. 01 L0
ENTER
para cambiar unid.
controlada
The first line shows the unit address. Click Enter to display a different unit.