We reserve the right to make changes without prior notice
77
Gestione serrandePl1
Tipo: PROPORZIONALE
Dampers control Pl1
Mode: PROPORTIONAL
Control compuertaPl1
Tipo: PROPORCIONAL
This mask allows to set the dampers control logic. “PROPORTIONAL” or “LINEAR” logic can be selected.
“PROPORTIONAL” is the factory set value.
Chiusura serranda
Pl2
A.E. in defrost:
Abilita: SI
Closing A.E. Pl2
damper in defrost
Enable: YES
Cierre de compuerPl2
ta de A.E.en defrost
Permittir: SI
This screen allows to enable the closure of the external air damper once the units in heat pump mode starts
the defrost.
T.est.rid.A.E.: Pl3
45.0
T.inv.rid.A.E.:
-05.0
T.sum.red.O.A.: Pl3
45.0
T.win.red.O.A.:
-05.0
T.ver.red.A.E.: Pl3
45.0
T.inv.red.A.E.:
-05.0
The screen allows to define the temperature range inside which the minimum external damper opening is set
to the value defined in the screen
Pl.
Outside this range, the minimum external damper opening is set to the value defined in the screen
Pl4.
Pl4
%aper.serr.A.E
in limitazione temp:
000%
Pl4
%open.damp.O.A
in temp. limitation:
000%
Pl4
%aper.red.A.E.:
en temp.restricción:
000%
The screen allows to set the minimum external damper opening once the outdoor temperature has value inside
the range defined in screen
Pl4.
Pm
Forza freecooling
all’accensione
(lavaggio) N
Pm
Force freecooling
at startup
(Washing) N
Pm
Forzar freecooling
al encender
(lavado) N
This screen is used to enable the washing function, i.e. Free cooling overriding upon unit start-up, in order to
change the ambient air.
The fourth line in the screen is used to enable the washing function.
Durata forzatura Po
Lavaggio 030min
Regol.temp./umidità
durante forzatura N
Washing Po
Forcing time 030min
Temperature regul.
during forcing N
Durac. forzado Po
Lavado 030min
Regul.temperatura
durante forzado N
This screen is used to set the washing cycle time and to enable temperature and humidity regulation during
this cycle.
The second line in the screen is used to set the washing cycle time.
The fourth line in the screen is used to either enable or disable temperature and humidity regulation during the
washing cycle.
Sbrinamento Pn
Rit.2 sbrin. 020min
Rit.inizio 000min
Tempo max 006min
Defrost Pn
Del.2 defrost 020min
Start delay 000min
Maximum time 006min
Desescarche Pn
Ret.2 desesc. 020min
Ret.inicio 000min
Tiemp màx 006min
This screen is used to set the delay between two consecutive defrost cycles, the delay before defrost is started
as soon as the defrost conditions are met, and the max. defrost cycle time.
The second line in the screen is used to set the delay before the defrost cycle gets started.
The third line in the screen is used to set the delay between two consecutive defrost cycles.
The fourth line in the screen is used to either enable or disable the max. defrost cycle time.