We reserve the right to make changes without prior notice
13
R
X-
/T
X+
R
X+
/T
X-
G
N
D
max 50 m
If the terminal connection distance is over 50 m, but no longer than 200 m, 3 pairs of braided wires should be
used, enclosed in a shielding having a cross-section of at least 0.5 sq.mm and T-switches (Carel code
TCONN6J000), as shown in the figure.
The pLAN network communicates through standard RS485 serial with baud-rate of 65.2 kbit/s. It uses the
Carel Multimaster protocol and can have a maximum extension of 500 m using T-switches for remoting.
T-switch
The cable connections must be made as indicated in the table below.
AWG24 cable (powered), cross-sect. 0.5 sq.mm
Terminal Function
Cable
connection
0 Earth
Shield
1 +
VRL
(30 Vdc)
First cable pair A
2
GND
Second cable pair A
3 Rx/Tx-
Third
cable
pair
A
4
Rx/Tx+
Third cable pair B
5
GND
Second cable pair B
6 +
VRL
(30 Vdc)
First cable pair B