SiUS181305E
Function of FFQ Series
Function
84
8.2
Thermostat Sensor in Remote Controller
Outline
Temperature is controlled by both the thermostat sensor in remote controller and air suction
thermostat in the indoor unit. (This is however limited to when the field setting for the thermostat
sensor in remote controller is utilized.)
Cooling
If there is a significant difference in the set temperature and the suction temperature, fine
adjustment control is carried out using a body thermostat sensor, or using the sensor in the remote
controller near the position of the user when the suction temperature is near the set temperature.
Assuming the set temperature in the figure above is 24°C (75.2
°
F), and the suction
temperature has changed from 18°C (64.4
°
F) to 30°C (86
°
F) (A
F):
(This example also assumes there are several other air conditioners, and the suction temperature
changes even when the thermostat sensor is off.)
18
23°C (64.4
73.4°F) (A
C): Body thermostat sensor is used.
23
27°C (73.4
80.6°F) (C
E): Remote controller thermostat sensor is used.
27
30°C (80.6
86°F) (E
F): Body thermostat sensor is used.
Assuming suction temperature has changed from 30
°
C (86
°
F) to 18
°
C (64.4
°
F) (F
A):
30
25°C (86
77°F) (F
D): Body thermostat sensor is used.
25
21°C (77
69.8°F) (D
B): Remote controller thermostat sensor is used.
21
18°C (69.8
64.4°F) (B
A): Body thermostat sensor is used.
Range in which thermostat sensor
in remote controller can be used
Range in which body
thermostat sensor can
be used
Differential
Suction temperature (TH1)
(R18811)
Set temperature (Ts)
12
14
16
18
20
22
24
26
28
30
32
34
53.6
57.2
60.8
64.4
68.0
71.6
75.2
78.8
82.4
86.0
89.6
93.2
°
C
°
F
°
C
32
30
28
26
24
22
20
18
16
°
F
89.6
86.0
82.4
78.8
75.2
71.6
68.0
64.4
60.8
TH1 = Ts + 1 (
°
C)
TH1 = Ts + 1.8 (
°
F)
TH1 = Ts + 3 (
°
C)
TH1 = Ts + 5.4 (
°
F)
TH1 = Ts – 3 (
°
C)
TH1 = Ts – 5.4 (
°
F)
TH1 = Ts – 1 (
°
C)
TH1 = Ts – 1.8 (
°
F)
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...