SiUS181305E
Field Settings
Test Operation and Field Settings
102
2.1.2 COOL/HEAT Changeover Setting by Dip Switches
The following field settings are made by dip switches on the service PCB.
Push the
BS2
(
SET
button) and match with the LEDs No. 1 - 15, push the
BS3
(
RETURN
button),
and confirm the data for each setting.
Data such as addresses and number of units is expressed as binary numbers; the two ways of
expressing are as follows:
The No. 1 cool / heat unified address is expressed as a binary
number consisting of the lower 6 digits. (0 - 63)
In the figure 1, the address is 010110 (binary number), which
translates to 16 + 4 + 2 = 22 (base 10 number). In other words, the
address is 22.
The number of terminal blocks for No. 12 and 13 is expressed as an
8-digit binary number, which is the combination of four upper, and
four lower digits for No. 12 and 13 respectively. (0 - 128)
In the figure 2, the address for No. 12 is 0101, the address for No. 13
is 0110, and the combination of the two is 01010110 (binary number),
which translates to 64 + 16 + 4 + 2 = 86 (base 10 number). In other
words, the number of terminal block is 86.
Refer to the preceding page for a list of data, etc. for No. 0 - 25.
l h l h l l h
16 4 1
32 8 2
l h h h l h l
64 16
128 32
No.12
l h h h l l h
4
1
No.13
8
2
(R12951)
(R12952)
Figure 1
Figure 2
Dip switch
Setting item
Description
No.
Setting
DS1-1
ON (OUT)
Cool / Heat
changeover
setting
It is used for changing over the unit which inputs the
COOL/HEAT switching command.
OFF (IN) (Factory
setting)
DS1-2
ON
Not used
Do not change the factory settings.
OFF (Factory setting)
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...