Test Operation
SiUS181305E
93
Test Operation and Field Settings
1.4
RA Indoor Unit: CTXS, FTXS, CDXS, FDXS Series
Outline
1. Measure the power supply voltage and make sure that it falls within the specified range.
2. Test operation should be carried out in either cooling or heating operation.
In cooling operation, select the lowest programmable temperature (18°C (64°F)); in heating
operation, select the highest programmable temperature (30°C (86°F)).
Test operation may be disabled in either operation mode depending on the room
temperature.
After test operation is complete, set the temperature to a normal level.
(26 ~ 28°C (78 ~ 82°F) in cooling, 20 ~ 24°C (68 ~ 75°F) in heating)
For protection, the system does not start for 3 minutes after it is turned off.
3. Carry out the test operation in accordance with the operation manual to ensure that all functions
and parts, such as louver movement, are working properly.
Note:
The air conditioner requires a small amount of power in standby mode. If the system is not to be
used for some time after installation, shut off the circuit breaker to eliminate unnecessary power
consumption.
If the circuit breaker trips to shut off the power to the air conditioner, the system backs up the
operation mode. The system then restarts operation with the previous operation mode when the
circuit breaker is restored.
Detail
ARC452 Series
(1) Press the
ON/OFF
button to turn on the system.
(2) Press the both of
TEMP
buttons and the
MODE
button at the same time.
(3) Press the
MODE
button twice.
(
T
is displayed on the screen to indicate that test operation is selected.)
(4) Press the
MODE
button and select the operation mode.
(5) Test operation terminates in approx. 30 minutes and switches into normal mode. To quit a test
operation, press the
ON/OFF
button.
(R14476)
(2)
(2) (3) (4)
(1) (5)
(2)
(3)
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...