Special Control
SiUS181305E
49
Function
3.4.1 Pump-down Residual Operation in Cooling Operation
3.4.2 Pump-down Residual Operation in Heating Operation
3.5
Restart Standby
Restart is prohibited to prevent frequent ON/OFF and to equalize pressure in the refrigerant system.
3.6
Stopping Operation
Operation of the actuator is cleared up when the system is down.
Actuator
Pump-down residual operation
Step 1
Step 2
Compressor
124 Hz Full load
52 Hz Full load
Outdoor fan
Fan control
Fan control
Four-way valve (Y1S)
OFF
OFF
Main electronic expansion valve (Y1E)
480 pulse
240 pulse
Subcooling electronic expansion valve (Y3E)
0 pulse
0 pulse
Hot gas bypass solenoid valve (Y2S)
OFF
OFF
Ending conditions
2 sec.
2 sec.
Actuator
Pump-down residual operation
Compressor
124 Hz Full load
Outdoor fan
STEP 7
Four-way valve (Y1S)
ON
Main electronic expansion valve (Y1E)
0 pulse
Subcooling electronic expansion valve (Y3E)
0 pulse
Hot gas bypass solenoid valve (Y2S)
OFF
Ending conditions
4 sec.
Actuator
Operation
Compressor
OFF
Outdoor fan
Ta > 30
C (86°F): STEP 4
Ta
30
C (86°F): OFF
Four-way valve (Y1S)
Former condition remains.
Main electronic expansion valve (Y1E)
0 pulse
Subcooling electronic expansion valve (Y3E)
0 pulse
Hot gas bypass solenoid valve (Y2S)
OFF
Ending conditions
2 min.
Actuator
Operation
Compressor
OFF
Outdoor fan
OFF
Four-way valve (Y1S)
Former condition remains.
Main electronic expansion valve (Y1E)
0 pulse
Subcooling electronic expansion valve (Y3E)
0 pulse
Hot gas bypass solenoid valve (Y2S)
OFF
Ending conditions
Indoor unit thermostat is turned ON.
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...