5. Other Control
5.1
Demand Control
In order to lower power consumption, the capacity of the outdoor unit is forcibly lowered using the
Demand 1 Setting.
To operate the unit with this mode, additional setting of Constant Demand Setting is necessary.
<Demand 1 setting>
Other protection control functions have precedence over the above operation.
5.2
Heating Operation Prohibition Control
Heating operation is prohibited when the outdoor temperature is above 24°CDB (75.2°FDB).
Setting
Standard for upper limit of power consumption
Demand 1 setting 1
Approx. 60%
Demand 1 setting 2 (factory setting)
Approx. 70%
Demand 1 setting 3
Approx. 80%