SiUS181305E
Troubleshooting for Outdoor Unit
Troubleshooting
222
7.33.3 Fan Motor Connector Check
Check No. 32
(1) Turn the power supply off.
(2) With the fan motor connector disconnected, measure the resistance between each pin, then
make sure that the resistance is more than the value mentioned in the following table.
Measurement point
Judgment
1 - 4
1 M
or more
2 - 4
100 k
or more
3 - 4
100
or more
4 - 7
100 k
or more
GND
(R15634)
(White) 1
(Orange) 2
(Brown) 3
(Blue) 4
(Unused) 5
(Unused) 6
(Red) 7
X106A, X107A
(M1F, M2F)