Troubleshooting for Outdoor Unit
SiUS181305E
185
Troubleshooting
Troubleshooting
Check No.30
Refer to P.220
1: Compare the voltages of the pressure sensor and the pressure gauge.
(For the voltage of the pressure sensor, measure the voltage at the connector, and then
convert it to pressure, referring to page 226.)
2: Measure the voltage of the pressure sensor.
Check No.30
NO
YES
YES
YES
NO
Is the
high pressure
switch operating value
normal (4.0 MPa
(1338 ftAq))?
NO
YES
NO
Check for the points shown below.
(1) Is the stop valve open?
(2) Is the high pressure switch connector properly connected to the main PCB (A1P)?
(3) Does the high pressure switch have continuity?
Are the
three points above
OK?
Rectify the defective points.
NO
YES
Are
the high pressure
value and the actual
measurement value by
pressure sensor
the same?
Replace the main PCB (A1P).
(1) Mount a pressure gauge on the high pressure service port.
(2) Reset the operation using the remote controller, and then restart the operation.
Does the stop
due to malfunction (
E3
)
recur?
Are the
characteristics of the
high pressure sensor
normal? (See
∗
1.)
Replace the high pressure switch.
Replace the high pressure sensor.
· The high pressure sensor is normal, and the pressure detected with the PCB is also normal.
· The high pressure has really become high.
Remove the causes by which the high pressure has become high.
Service Checker
Connect the service checker to compare the high pressure value and the actual measurement
value by pressure sensor by using the service checker. (See
∗
2)
(R19092)
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
+5V
GND
(4)
(3)
(2)
(1)
X17A (Red)
High
pressure
sensor
Microcomputer
A/D input
Measure the voltage here.
Red
Black
White
(R19189)
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...