Field Settings
SiUS181305E
117
Test Operation and Field Settings
2.3.4 Address and MAIN / SUB Setting for Wireless Remote Controller
Outline
If several wireless remote controller units are used together in the same room (including the case
where both group control and individual remote controller control are used together), be sure to set
the addresses for the receiver and wireless remote controller. (For group control, see the attached
installation manual for the indoor unit.) If using together with a wired remote controller, you have to
change the MAIN / SUB setting on the signal receiver PCB.
Signal Receiver
PCB
Set the address setting switch (SS2) on the signal receiver PCB according to the table below.
When using both a wired and a wireless remote controller for 1 indoor unit, the wired controller
should be set to MAIN. Therefore, set the MAIN / SUB setting switch (SS1) on the signal receiver
PCB to SUB.
After completing setting, seal off the opening of the address setting switch (SS2) and the MAIN / SUB
setting switch (SS1) with the attached sealing pad.
Unit No.
No.1
No.2
No.3
Address setting switch
(SS2)
123
(S1935)
123
(S1936)
123
(S1937)
MAIN
SUB
MAIN / SUB setting
switch (SS1)
S
M
(S1938)
S
M
(S1939)
1 2 3 M S
SS2 SS1
(S1940)
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...