Service Check Function
Troubleshooting
146
Check Method 2
1. Press the 3 buttons (
TEMP
,
TEMP
,
MODE
) at the same time to enter the diagnosis mode.
The left-side number blinks.
2. Press the
TEMP
or
button and change the number until you hear the two consecutive
beeps or the long beep.
3. Diagnose by the sound.
beep : The left-side number does not correspond with the error code.
two consecutive beeps : The left-side number corresponds with the error code but the
right-side number does not.
long beep : Both the left-side and right-side number correspond with the error code.
The numbers indicated when you hear the long beep are the error code.
Error codes and description
Refer to page 154, 155.
4. Press the
MODE
button.
The right-side number blinks.
(R14550)
(R9430)
(R14551)
(R14552)
(R9429)