2.3.2 Overview of the Field Settings
: factory setting
Note:
1. Field settings are normally applied to the entire remote control group, however if individual
indoor units in the remote control group require specific settings or for confirmation that settings
have been established, utilize the mode number in parenthesis.
2. Any features not supported by the installed indoor unit will not be displayed.
3. When mode 10-2-01 is selected, only the return air temperature value is reported to the
multizone controller.
4. The actual default value will depend upon the indoor unit model.
Mode
No.
(Note 1)
First
Code
No.
Description of setting
Second Code No. (Note 2)
01
02
03
04
10 (20)
0
Filter
cleaning
sign interval
Longlife
filter
Lig
ht
Approx.
2,500
hrs.
Hea
v
y
Approx.
1,250
hrs.
—
—
2
Priority of thermistor
sensors for space
temperature control
The return air
thermistor is
primary and
the remote
controller
thermistor is
secondary.
The remote
controller
thermistor is
not utilized.
Only the
return air
thermistor will
be utilized.
Only the
remote
controller
thermistor will
be utilized.
—
3
Filter cleaning sign
Display
No display
—
—
5
Room temperature
value reported to
multizone controllers
Return air
thermistor
Thermistor
designated
by 10-2
above
(Note 3)
—
—
12 (22)
1
Forced ON/OFF from
outside function
Forced OFF
ON/OFF
operation
—
—
2
Thermostat differential
changeover (setting
for when using remote
sensor) (Note 4)
1°C
(2°F)
0.5°C
(1°F)
—
—
13 (23)
1
Selection of airflow
direction (setting for
when a blocking pad
kit has been installed)
4-way flow
3-way flow
2-way flow
—
4
Airflow direction range
setting
Upper
Normal
Lower
—
1c
1
Thermistor sensor for
auto changeover and
setback control by the
remote controller
Utilize the
return air
thermistor
Utilize the
remote
controller
thermistor
—
—
3
Access permission
level setting
Level 2
Level 3
—
—
1e
2
Setback availability
N/A
Heat only
Cool only
Cool/Heat
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...