Troubleshooting for Outdoor Unit
SiUS181305E
183
Troubleshooting
7. Troubleshooting for Outdoor Unit
7.1
Outdoor Unit PCB Abnormality
Error Code
E1
Method of Error
Detection
Check data from EEPROM
Error Decision
Conditions
When data could not be correctly received from the EEPROM
EEPROM: Type of nonvolatile memory. Maintains memory contents even when the power supply is
turned off.
Supposed
Causes
Defective main PCB (A1P)
Troubleshooting
Turn OFF the power supply
once and then turn it ON
again.
Does it return to
normal?
Could be other causes than
malfunction (for example,
noise etc.).
Replace the main PCB
(A1P).
(R15335)
YES
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.