Troubleshooting with LED
SiUS181305E
141
Troubleshooting
<Selection of check item>
<Monitor mode>
<Confirmation of malfunction 1>
Press the
MODE
(
BS1
) button and
enter the monitor mode.
Press the
SET
(
BS2
) button and
select a check item according to the
LED pattern of No.14~16 and
No.20~22.
Refer to page 102 for check items.
Press the
RETURN
(
BS3
) button
once to display the first digit of error
code.
<Confirmation of malfunction 2>
Press the
SET
(
BS2
) button once to
display the second digit of error
code.
Press the
RETURN
(
BS3
) button
and return to the initial status of
monitor mode.
<Confirmation of malfunction 3>
Press the
SET
(
BS2
) button once to
display the malfunction location.
Detail
description
on next
page.
<Confirmation of malfunction 4>
Press the
SET
(
BS2
) button once to
display the malfunction unit and the
malfunction location.
∗
If you become unsure of how to
proceed, press the
MODE
(
BS1
)
button and return to the setting
mode 1.
Contents of malfunction
Error
code
High voltage of capacitor in main
inverter circuit
Imbalance of inverter power supply voltage
P1
Radiation fin thermistor abnormality
Faulty thermistor of inverter fin
P4
Low pressure drop due to refrigerant
shortage or electronic expansion valve
abnormality
Refrigerant shortage alarm
U0
Power supply insufficient or
instantaneous failure
Insufficient Inverter voltage
U2
Faulty charge of capacitor in main inverter circuit
Malfunction due to SP-PAM overvoltage
Malfunction due to P-N short circuit
Check operation is not conducted.
U3
Transmission error between indoor
unit and BP unit
I/O transmission error
U4
I/O transmission error
Transmission error between indoor
unit and outdoor unit in the same
system
Indoor unit system abnormal in other system
or other indoor unit system abnormal in own
system
U9
Field setting switch abnormality or
Excessive number of indoor units
System transmission malfunction
UA
Overconnection malfunction of indoor units
Malfunction of field setting
Refrigerant abnormal
Connection error (BP unit)
System abnormality, refrigerant
system address undefined
Wiring error (Auto-address error)
UH
System is not set yet
Conflict in wiring and piping
UF
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...