SiUS181305E
Branch Provider (BP) Unit Control
Function
58
6.2
Branch Provider (BP) Unit Electronic Expansion Valve
Control
This function provides instructions regarding the absolute flow rate, relative flow rate and fully
closing from the outdoor unit to the BP unit in order to ensure outdoor unit compressor safety and
optimum refrigerating cycle of the system.
With the transmission a permit/prohibit flag for each distribution control in the BP unit, the
distribution control startup timing is controlled by the outdoor unit.
6.2.1 Electronic Expansion Valve Initial Opening Setting
Outline
This function improves stability of the system to set initial opening of the electronic expansion valve
at starting operation.
When the EV opening command from outdoor unit is lifted, the following opening setting is
performed.
Detail
<Cooling Operation>
Tr: room thermistor temperature
Ta: outdoor temperature
<Heating Operation>
Target opening = 350 pulse
6.2.2 Electronic Expansion Valve Flow Rate Restriction
Outline
This function prevents deviation from the specified electronic expansion valve range by restricting
the electronic expansion valve flow rates of the operating and non-operating indoor units during
compressor operation. It also prevents the generation of abnormal noise such as refrigerant flowing
sound by restricting the circulation of refrigerant according to the operating conditions (unit ON/
OFF) of indoor units.
Detail
Restriction of electronic expansion valve opening degrees of operating indoor units;
... Restriction of maximum and minimum flow rates based on constant
Restriction of electronic expansion valve opening degrees of non-heating indoor units;
... Restriction of minimum flow rate based on constant
... Maximum flow rate determined based on flow rates of operating indoor units
A
B
07 ~ 12 class
140
Ta
Tr
0
15 ~ 18 class
156
Tr
Ta
2.5
24 class
170
5
2
25
18
286
5
5
9
Target opening (pulse) = × (Tr (˚C) – 14) +
A
–
B
× (Ta (˚C) – Tr (˚C))
= × (Tr (˚F) – ) +
A
–
B
× × (Ta (˚F) – Tr (˚F))
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...