Field Settings
SiUS181305E
101
Test Operation and Field Settings
Monitor Mode
The numbers in the No. column represent the number of times to press the
SET
(
BS2
) button.
Note:
Various Settings
No.
Check item
LED display
Data display
H1P
H2P
H3P
H4P
H5P
H6P
H7P
0
Various setting
l
h
h
h
h
h
h
See the note
below.
1
Cool / heat unified address
l
h
h
h
h
h
k
Lower 6 digits
2
Low noise / demand address
l
h
h
h
h
k
h
3
Not used
l
h
h
h
h
k
k
4
AIRNET address
l
h
h
h
k
h
h
5
Number of connected indoor units
l
h
h
h
k
h
k
7
Number of connected zone units
(excluding outdoor and BS unit)
l
h
h
h
k
k
k
8
Number of outdoor units
l
h
h
k
h
h
h
11
Number of zone units (excluding
outdoor and BS unit)
l
h
h
k
h
k
k
Lower 6 digits
12
Number of terminal blocks
l
h
h
k
k
h
h
Lower 4 digits:
upper
13
Number of terminal blocks
l
h
h
k
k
h
k
Lower 4 digits:
lower
14
Contents of malfunction (the latest)
l
h
h
k
k
k
h
Error code table
15
Contents of malfunction
(1 cycle before)
l
h
h
k
k
k
k
16
Contents of malfunction
(2 cycle before)
l
h
k
h
h
h
h
20
Contents of retry (the latest)
l
h
k
h
k
h
h
21
Contents of retry (1 cycle before)
l
h
k
h
k
h
k
22
Contents of retry (2 cycle before)
l
h
k
h
k
k
h
25
Normal judgment of outdoor units
PCB
l
h
k
k
h
h
k
Lower 2 digits:
k h
Abnormal
h k
Normal
h h
Undetermined
<Selection of check item>
<Confirmation on check item>
Press the
MODE
(
BS1
) button and
enter the monitor mode.
Press the
SET
(
BS2
) button and
select a check item according to the
LED pattern.
Press the
RETURN
(
BS3
) button to
display different data of check item.
Press the
RETURN
(
BS3
) button
and return to the initial status of
monitor mode.
∗
If you become unsure of how to
proceed, press the
MODE
(
BS1
)
button and return to the setting
mode 1.
H1P H2P H3P H4P H5P H6P H7P
Emergency operation /
backup operation setting
ON
l
h
h
k
h
h
h
OFF
l
h
h
h
h
h
h
Defrost select setting
Short
l
h
h
h
k
h
h
Medium
l
h
h
h
l
h
h
Long
l
h
h
h
h
h
h
Te setting
H
l
h
h
h
h
k
h
M
l
h
h
h
h
l
h
L
l
h
h
h
h
h
h
Tc setting
H
l
h
h
h
h
h
k
M
l
h
h
h
h
h
l
L
l
h
h
h
h
h
h
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...