Troubleshooting with LED
SiUS181305E
139
Troubleshooting
Error code indication in monitor mode
<Selection of check item>
<Monitor mode>
<Confirmation of malfunction 1>
Press the
MODE
(
BS1
) button and
enter the monitor mode.
Press the
SET
(
BS2
) button and
select a check item according to the
LED pattern of No.14~16 and
No.20~22.
Refer to page 102 for check items.
Press the
RETURN
(
BS3
) button
once to display the first digit of error
code.
<Confirmation of malfunction 2>
Press the
SET
(
BS2
) button once to
display the second digit of error
code.
Press the
RETURN
(
BS3
) button
and return to the initial status of
monitor mode.
<Confirmation of malfunction 3>
Press the
SET
(
BS2
) button once to
display the malfunction location.
Detail
description
on next
page.
<Confirmation of malfunction 4>
Press the
SET
(
BS2
) button once to
display the malfunction unit and the
malfunction location.
∗
If you become unsure of how to
proceed, press the
MODE
(
BS1
)
button and return to the setting
mode 1.
Contents of malfunction
Error
code
Outdoor unit PCB abnormality
Detection of DIII-Net
E1
Actuation of high pressure switch
High pressure switch activated (S1PH)
E3
Actuation of low pressure sensor
Abnormal Pe
E4
Compressor motor lock
Detection of compressor lock
E5
Outdoor fan motor abnormality
Detection of fan motor lock (M1F)
E7
Detection of fan motor lock (M2F)
Moving part of electronic expansion
valve (Y1E, Y3E) abnormality
Y1E (main)
E9
Y3E (subcooling)
Outdoor temperature thermistor (R1T)
abnormality
Short or open circuit (R1T)
H9
Discharge pipe temperature
abnormality
Abnormal Tdi
F3
Refrigerant overcharged
Refrigerant overcharge
F6
Discharge pipe thermistor (R2T)
abnormality
Short or open circuit (R2T)
J3
Suction pipe thermistor (R3T, R5T)
abnormality
Short or open circuit (suction 1: R3T)
J5
Short or open circuit (suction 2: R5T)
Outdoor heat exchanger thermistor
(R4T) abnormality
Short or open circuit (R4T)
J6
Outdoor liquid pipe thermistor (R7T)
abnormality
Short or open circuit (R7T)
J7
Subcooling heat exchanger gas pipe
thermistor (R6T) abnormality
Short or open circuit (R6T)
J9
High pressure sensor abnormality
Short or open circuit (S1NPH)
JA
Low pressure sensor abnormality
Short or open circuit (S1NPL)
JC
Outdoor unit PCB abnormality
Faulty IPM
L1
Abnormal current sensor offset
Abnormal IGBT
Faulty current sensor
Abnormal SP-PAM overvoltage
Radiation fin temperature rise
Overheating (FINTH)
L4
Inverter compressor abnormality
Inverter instantaneous overcurrent
L5
Inverter current abnormality
Electronic thermal switch 1
L8
Electronic thermal switch 2
Out-of-step
Speed down after startup
Lightening detection
Compressor start-up error
Stall prevention (Current increasing)
L9
Stall prevention (Faulty start up)
Abnormal waveform in startup
Out-of-step
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...