Troubleshooting for Outdoor Unit
SiUS181305E
219
Troubleshooting
7.32 System Abnormality, Refrigerant System Address
Undefined
Error Code
UH
Method of Error
Detection
The system detects an indoor unit to which auto address has not been assigned.
Error Decision
Conditions
The malfunction decision is made as soon as the abnormality is detected.
Supposed
Causes
Improper connection of transmission wiring between indoor and outdoor unit
Defective indoor unit PCB
Defective main PCB (A1P)
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
YES
After fixing incorrect wiring,
push and hold the RESET
button (BS5) on the service
PCB (A2P) for 5 seconds.
∗
The unit does not run for up
to 12 minutes.
Normal
NO
YES
Normal
NO
Does a malfunction
occur?
NO
YES
NO
YES
Replace the indoor unit PCB.
Replace the main PCB (A1P).
After fixing incorrect wiring,
push and hold the RESET
button on the outdoor unit
PCB for 5 seconds.
Is the
electricity
being introduce for
the first time after
installation or after an indoor
or outdoor unit PCB
has been
replaced?
Does
a malfunction
occur even after 12
minutes elapses from the
time when electricity is
introduced to indoor
unit and outdoor
unit?
Is the
indoor unit - outdoor unit
transmission wiring
normal?
Does
a
UH
malfunction occur
for all indoor units in
the system?
(R15644)
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...