Branch Provider (BP) Unit Control
SiUS181305E
59
Function
6.2.3 Full Closing of Electronic Expansion Valves
Outline
The electronic expansion valves are initialized when the power is turned on.
Detail
The following processes are conducted.
1. Conducts P1 pulses close when power is turned on, and sets current opening to 0 pulse (fully
closing process).
2. Sends electronic expansion valve initialization signal to outdoor unit.
3. Closes the electronic expansion valve of each chamber (sets the electronic expansion valve
pulse to 0).
4. Stops transmission of electronic expansion valve initialization signal when EVH (bypass
electronic expansion valve) retightening is completed.
6.2.4 Control Based on EV Opening Command from Outdoor Unit
Outline
This function operates the electronic expansion valve based on EV opening command sent from
the outdoor unit.
Detail
The electronic expansion valve operation based on EV opening command provides the following
functions.
1) Pressure equalization prior to startup
2) Startup control
3) Restart standby
4) Pump-down residual operation
5) Oil return operation
6) Defrosting operation
P 1
P 1
0
0
P 1
0
P 1
0
EVA
EVB
EVC
EVH
(M1047)
Power ON
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...