SiUS181305E
Test Operation
Test Operation and Field Settings
90
1.1.4 Confirmation on Normal Operation
Conduct normal unit operation after the check operation has been completed.
(When outdoor air temperature is 24°CDB (75.2°FDB) or higher, the unit can not be operated
with heating operation. See the installation manual attached.)
Confirm that the indoor/outdoor units can be operated normally.
(When an abnormal noise due to liquid compression by the compressor can be heard, stop the
unit immediately, and turn on the crankcase heater to heat up it sufficiently, then start operation
again.)
Operate indoor unit one by one to check that the corresponding outdoor unit operates.
Confirm that the indoor unit discharges cold air (or warm air).
Operate the air direction control button and flow rate control button to check the function of the
devices.
1.2
Operation when Power is Turned On
1.2.1 When Turning On Power First Time
The unit cannot be run for up to 12 minutes to automatically set the master power and address
(indoor-outdoor address, etc.).
Status
1.2.2 When Turning On Power the Second Time and Subsequent
Push the
RESET
(
BS5
) button on the outdoor unit PCB. Operation becomes possible for about 2
minutes. If you do not push the
RESET
button, the unit cannot be run for up to 10 minutes to
automatically set master power.
Status
1.2.3 When an Indoor Unit or Outdoor Unit has been Added, or Indoor or
Outdoor Unit PCB has been Changed
Be sure to push and hold the
RESET
button for 5 seconds. If not, the addition cannot be
recognized. In this case, the unit cannot be run for up to 12 minutes to automatically set the
address (indoor-outdoor address, etc.)
Status
Outdoor unit
Test lamp H2P .... Blinks
Can also be set during operation described above.
Indoor unit
If the
ON
button is pushed during operation described above, the
UH
malfunction
indicator blinks.
(Returns to normal when automatic setting is complete.)
Outdoor unit
Test lamp H2P .... Blinks
Can also be set during operation described above.
Indoor unit
If the
ON
button is pushed during operation described above, the operation lamp
lights but the compressor does not operate. (Returns to normal when automatic
setting is complete.)
Outdoor unit
Test lamp H2P .... ON
Can also be set during operation described above.
Indoor unit
If the
ON
button is pushed during operation described above, the
UH
or
U4
malfunction indicator blinks. (Returns to normal when automatic setting is
complete.)
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...