SiUS181305E
Special Control
Function
46
3.2
Oil Return Operation
In order to prevent the compressor from running out of oil, the oil return operation is conducted to
recover oil flown out from the compressor to the system side.
3.2.1 Oil Return Operation in Cooling Operation
<Conditions to start>
Oil return operation in cooling operation is started referring to the following conditions:
Cumulative oil feed rate
Timer setting (Make this setting so as to start the oil return operation when the initial cumulative
operating time reaches 2 hours after power supply is turned ON and then every 8 hours.)
The cumulative oil feed rate is computed from Tc, Te, and compressor loads.
Outdoor unit actuator
Oil return preparation
operation
Oil return operation
Post-oil-return operation
Compressor
Take the current step as the
upper limit.
52 Hz Full load (
Low
pressure constant control)
Same as in
oil return
operation mode.
Outdoor fan
Fan control (Normal cooling) Fan control (Normal cooling) Fan control (Normal cooling)
Four-way valve (Y1S)
OFF
OFF
OFF
Main electronic expansion valve (Y1E) 480 pulse
480 pulse
480 pulse
Subcooling electronic expansion valve
(Y3E)
SH control
0 pulse
0 pulse
Hot gas bypass solenoid valve (Y2S)
OFF
OFF
OFF
Ending conditions
20 sec.
3 min.
Ts1 – Te < 5
C
(9°F)
3 min.
Pe < 0.6 MPa
(201 ftAq)
HTdi > 110
C
(230°F)
or
or
Indoor unit actuator
Cooling oil return operation
Indoor fan
Thermostat ON unit
Remote controller setting
Stopping unit
OFF
Thermostat OFF unit
Remote controller setting
Electronic expansion valve of
BP unit
Thermostat ON unit
SH control
Stopping unit
77 pulse
Thermostat OFF unit
SH control
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...