Field Settings
SiUS181305E
103
Test Operation and Field Settings
(1) Set Cool/Heat Separately for Each Outdoor Unit System by Indoor Unit Remote Controller
It does not matter whether or not there is outdoor - outdoor unit wiring.
Set the dip switch DS1-1 of the outdoor unit PCB (A2P) to
IN
(factory setting).
Set cool/heat switching to
IND
(individual) in the setting mode 1 (factory setting).
MODE
TEST
ERROR
C/H SELECT
C/H SELECTOR
IND
MASTER
SLAVE
H2P
H1P
H3P
H4P
H5P
H6P
H7P
L.N.O.P.
DEMAND
OUT
A2P
IN
Dip SW.
DS1-1
O
I
BP unit
F1 F2
Indoor
unit
Remote
controller
Remote
controller
(R17941)
C/H SELECTOR
A4P
TO BP UNIT
TO OUTDOOR
UNIT
X2M
A
B
C
F1
F2
F1
F2
P1 P2
Indoor
unit
P1 P2
BP unit
F1 F2
<Set the master unit (= indoor unit having the right to
select the cooling / heating operation mode).>
In the case of wired remote controllers
• After the check operation,
CHANGEOVER UNDER
CONTROL
is flashing in all connected remote controllers.
• Select an indoor unit to be used as the master unit in
accordance with the request from the customer.
(It is recommended to select an indoor unit which will be used
most often as the master unit.)
• Press the operation mode selector button in the remote
controller of the indoor unit selected as the master unit.
• In that remote controller,
CHANGEOVER UNDER CONTROL
disappears. That remote controller controls changeover of the
cooling / heating operation mode.
• In other remote controllers,
CHANGEOVER UNDER
CONTROL
lights.
For the details, refer to the installation manual supplied
together with the indoor unit.
In the case of wireless remote controllers
• After the check operation, the timer lamp is flashing in all
connected indoor units.
• Select an indoor unit to be used as the master unit in
accordance with the request from the customer.
(It is recommended to select an indoor unit which will be used
most often as the master unit.)
• Press the operation selector mode button in the remote
controller of the indoor unit selected as the master unit. A peep
sound is emitted, and the timer lamp turns off in all indoor
units.
• That indoor unit controls changeover of the cooling / heating
operation mode.
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...