SiUS181305E
Field Settings
Test Operation and Field Settings
98
Setting Mode 2
The numbers in the No. column represent the number of times to press the
SET
(
BS2
) button.
No.
Setting item
Description
1
Cool / heat unified
address
Sets address for cool / heat unified operation.
2
Low noise / demand
address
Address for low noise / demand operation
3
Test operation
settings
Used to conduct test operation without making changes to
the PCB and replacing the refrigerant, after the completion
of maintenance.
5
Indoor unit forced
fan H
Allows forced operation of indoor unit fan while unit is
stopped. (H tap)
6
Indoor unit forced
operation
Allows forced operation of indoor unit.
8
Te setting
Target evaporation temperature for cooling
9
Tc setting
Target condensation temperature for heating
10
Defrost changeover
setting
Changes the temperature condition for defrost and sets to
quick defrost or slow defrost.
12
External low noise
setting / Demand
setting
Reception of external low noise or demand signal
13
AIRNET address
Set address for AIRNET.
16
Setting of hot water
heater
Make this setting to conduct heating operation with hot
water heater.
20
Additional refrigerant
charge operation
setting
Carries out additional refrigerant charge operation.
21
Refrigerant
recovery /
vacuuming mode
setting
Sets to refrigerant recovery or vacuuming mode.
22
Night-time low noise
setting
Sets automatic nighttime low noise operation in a simple
way.
The operating time is based on Starting Set and Ending Set.
25
Setting of low noise
level
Sets low noise level when the low noise signal is received.
26
Night-time low noise
operation start
setting
Sets starting time of nighttime low noise operation.
(Night-time low noise setting is also required.)
27
Night-time low noise
operation end
setting
Sets ending time of nighttime low noise operation.
(Night-time low noise setting is also required.)
28
Power transistor
check mode
Check after
disconnection of
compressor wires
Used for trouble diagnosis of DC compressor. Since the
waveform of inverter is output without wiring to the
compressor, it is convenient to probe whether the trouble
comes from the compressor or PCB.
29
Capacity
precedence setting
If the capacity control is required, the low noise control is
automatically released by this setting during carrying out low
noise operation and nighttime low noise operation.
30
Demand setting 1
Changes target value of power consumption when demand
control 1 is received.
32
Constant demand
setting
Enables demand control 1 without external input. (Effective
to prevent a problem that circuit breaker of small capacity is
shut down due to large load.)
<Selection of setting items>
<Selection of setting conditions>
Press the
MODE
(
BS1
) button for 5
seconds and enter the setting mode
2.
Press the
SET
(
BS2
) button and
select a setting item according to the
LED pattern shown in the table on
the right.
↓
Press the
RETURN
(
BS3
) button
and decide the item. (The present
setting condition is shown.)
Press the
RETURN
(
BS3
) button
and return to the initial status of
setting mode 2.
∗
If you become unsure of how to
proceed, press the
MODE
(
BS1
)
button and return to the setting
mode 1.
Press the
SET
(
BS2
) button and
select to the setting condition you
want.
↓
Press the
RETURN
(
BS3
) button and
decide the condition.
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...