Troubleshooting for FFQ Series
SiUS181305E
171
Troubleshooting
5.5
Thermistor or Related Abnormality
Error Code
C4, C5, C9
Method of Error
Detection
The temperatures detected by the thermistors determine thermistor errors.
Error Decision
Conditions
The thermistor input is more than 4.96 V or less than 0.04 V during compressor operation.
Supposed
Causes
Disconnection of connector
Defective thermistor corresponding to the error code
Defective indoor unit PCB
Troubleshooting
If the cause of the problem is related to the thermistors, the thermistors should be checked prior to
changing the indoor unit PCB.
To check the thermistors, proceed as follows:
C4
: Indoor heat exchanger thermistor 1 (liquid pipe) (R2T)
C5
: Indoor heat exchanger thermistor 2 (R3T)
C9
: Room temperature thermistor (R1T)
Refer to Thermistor Resistance / Temperature Characteristics table 1 on page 224.
Step
Action
1
Disconnect the thermistor from the indoor unit PCB.
2
Read the temperature and the resistance value.
3
Check if the measured values correspond with the values in the table of thermistor
resistance check.
YES
(R19138)
NO
Check the thermistor resistance
value.
YES
NO
Caution
Correct the connection.
Replace the thermistor.
(Replace the indoor unit PCB.)
Replace the indoor unit PCB.
Is it normal?
Is it normal?
Check the connection of
connectors.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...