Field Settings
SiUS181305E
97
Test Operation and Field Settings
Setting Mode 1
This mode is used to set and check the following items.
1. Set items ············ In order to make COOL/HEAT selection in a batch of outdoor unit group, change the setting.
• COOL/HEAT selection (IND) ·····················Used to select COOL or HEAT by individual outdoor unit
(factory setting).
• COOL/HEAT selection (MASTER) ············Used to select COOL or HEAT by outdoor unit group with
the master unit.
• COOL/HEAT selection (SLAVE)················Used to select COOL or HEAT by outdoor unit group with
the slave unit.
2. Check items ······· The following items can be checked.
(1) Current operating conditions (Normal / Abnormal / In check operation)
(2) Setting conditions of COOL/HEAT selection (Individual / Batch master / Batch slave)
(3) Low noise operating conditions (In normal operation / In low noise operation)
(4) Demand operating conditions (In normal operation / In demand operation)
Procedure for changing COOL/HEAT selection setting
Press the
SET
(
BS2
) button to set
the blinking LED according to the
pattern shown on the right.
Press the
RETURN
(
BS3
) button to
determine the setting.
Check the system for each condition
through LED displays. (Refer to
information in table on the right.)
Press the
RETURN
(
BS3
) button and
return to the initial status of setting
mode 1.
h
h
h
h
h
h
l
h
h
h
l
h
h
h
l
h
h
h
h
h
h
k
ON
h
OFF
l
Blink
Procedure for checking
Setting mode 1 is the initial status
(normal). In case of other status,
press the
MODE
(
BS1
) button one
time and return to the setting mode 1.
MODE
H1P
TEST
H2P
COOL/HEAT select
IND
H3P
MASTER
H4P
SLAVE
H5P
Low
noise
H6P
Demand
H7P
h
h
k
h
h
h
h
Setting (displaying) item
MODE
H1P
TEST
H2P
COOL/HEAT select
IND
H3P
MASTER
H4P
SLAVE
H5P
LOW
NOISE
H6P
DEMAND
H7P
For selection by individual outdoor unit (factory setting)
For selection in a batch of outdoor unit group with master unit
For selection in a batch of outdoor unit group with slave unit
The system returns to the initial status of setting mode 1.
Current operating conditions
h
Normal
k
Abnormal
l
In preparation or in
check operation
Setting of COOL/HEAT selection
k h h
By individual outdoor
unit
h k h
In a batch of outdoor unit
group with master unit
h h k
In a batch of outdoor unit
group with slave unit
Low noise operating conditions
h
In normal operation
k
In low noise operation
Demand operating conditions
h
In normal operation
k
In demand operation
(R15637)
(R15638)
Setting mode 1 is the initial status
(normal). In case of other status,
press the
MODE
(
BS1
) button one
time and return to the setting mode 1.
Содержание RMXS-L Series
Страница 10: ...Safety Considerations Safety Considerations ix...
Страница 11: ...SiUS181305E 1 List of Functions Part 1 List of Functions 1 Functions 2 1 1 Outdoor Unit 2 1 2 Indoor Unit 3...
Страница 129: ...SiUS181305E Field Settings Test Operation and Field Settings 120...
Страница 144: ...FFQ09 12 15 18LVJU SiUS181305E 135 Remote Controller...
Страница 249: ...SiUS181305E Removal Procedure Booklet No Appendix 240...