2
−
16
62-11389
2.7.3 Remote Temperature Sensors
The unit is provisioned to connect up to three remote
temperature sensors directly to the microprocessor.
The microprocessor may be configured to display the
sensor reading in the Unit Data and to record the sensor
reading in the DataLink data recorder. A user specified
name may be configured for each sensor. This name will
be displayed, rather than the default Remote Sensor #1,
Remote Sensor #2 or Remote Sensor #3 name, in the
unit data list.
2.7.4 Remote Control Panel
The unit may be fitted with, and the remote switch/door
switch configurations set for, an optional remote control
panel. The panel displays refrigerated compartment set
point, compartment temperature and operating mode
(heat, cool or defrost). The set point may be set and the
unit may be started and stopped using the remote panel.
This compact panel can be mounted to suit the
individual operator’s preferences - for example, flush
mounted inside the trailer near the rear door. Refer to
Section 3.20.2 for more information on the remote
control panel.
NOTE
The remote switch/door switch configurations
may be set for use as individual switches or for
use with a remote panel, not both.
2.8 ENGINE DATA
Engine Model
V2203L-DI-E3B-CTD-5 (26-00128-15)
Displacement
135 in
3 (
2.2 liters)
No. Cylinders
4
Rated Power
32 hp (24 KW) @1800 rpm
NOTE: Refer to Table 2-1 for engine speed settings
Weight
440 lbs (199.6 kg)
Coolant Capacity
2 U.S. gallons (7.6 liters)
- 50/50 mix ethylene glycol antifreeze (with inhibitors) -
never to exceed 60/40
CAUTION
Use only ethylene glycol anti-freeze (with inhibitors) in system as glycol by
itself will damage the cooling system. Always add pre-mixed 50/50 anti-
freeze and water to radiator / engine. Never exceed more than a 60% con-
centration of anti-freeze. Use a low silicate anti-freeze meeting GM specifi-
cations GM 6038M for standard life coolant or use Texaco Havoline ex-
tended life coolant or any other extended life coolant which is Dexcool ap-
proved and has 5/150 (5 years / 150,000 miles) on the label.
Thermostat
Starts to open 177 to 182
F (81 to 83
C). Fully open at 203
F (95
C).
Fuel System
Fuel
Winter: Diesel No. 1 Summer: Diesel No. 2(Maximum 5% Bio-Diesel is also allowed)
Fuel Heater
Temperature Switch
Close on a temperature fall @ 45
F (7.2
°
C)
Open on a temperature rise @ 75
F (24
°
C)
Firing Order
1-3-4-2
Intake Air Heater
Amperage
42 amps at 12 VDC
Lubrication System
Oil Pressure
40 to 62 psig (2.8 To 4.2 Bar) - Engine in high speed
Oil Pressure Switch
(ENOPS)
Closes, on pressure rise, at 18 psig (1.22 Bar)
Opens, on pressure fall, at 12 psig (0.82 Bar)
Oil Capacity with Filter
15 quarts (14.2 liters)
Lube Oil Viscosity:
API CG or better
OR
Mobil Delvac 1
Outdoor Temperature
Grade (SAE)
Below 32
F (0
°
C)
10W30 or Mobil Delvac 1 (5W 40)
Above 32
F (0
C)
10W30 or Mobil Delvac 1 (5W 40)
or 15W 40
Oil Change Intervals
Refer to Section 8.2 for information on service intervals.