Alarm
NO.
Steps
Alarm/Cause
Corrective Action
7.5 START UP / ENGINE ALARMS
30
FAILED TO RUN MINIMUM TIME
•
TRIGGER–ON: The unit has shutdown on an alarm 3 times without having run for at least 15
minutes between each shutdown (not including Door shutdowns.)
•
UNIT CONTROL:
Engine Operation: engine and unit shutdown and alarm.
Standby Operation: refrigeration system shutdown and alarm with PSCON
still energized.
•
RESET CONDITION: Alarm may be manually reset via keypad or by turning the unit off, then back on
again. If the Unit Operation configuration is set to Rail Mode, this alarm will reset after 4 hours.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (See Note 1 page 7
−
2.) Operate the unit through the appropriate modes to see if any active alarm
occurs. Continue with the steps below as necessary.
Check For Alarms
Check for shutdown alarms.
Alarm conditions must be corrected and the alarm(s)
cleared to continue.