62-11389
5
−
11
2. After the unit specific and time sensitive
configuration settings are complete use the
UP or DOWN ARROW keys until
“CONFIGS COMPLETE, = TO EXIT” is
displayed in the MessageCenter. Press the
= key to save.
3. If the Configurations, Functional
Parameters and DataLink data recorder
setup will be set from the keypad and /or
ReeferManager, continue with following
steps.
5.7.4 Configurations Via Keypad
a. Refer to Section 5.2 for a list of available micropro-
cessor Configurations. Refer to Section 5.2.1 for in-
structions on how to access them.
5.7.5 Functional Parameters Via Keypad
a. Refer to Section 3.15 for list of available Micropro-
cessor Functional Parameters and for directions on
how to access them.
b. Leave the microprocessor powered up as you con-
tinue with the next section.
5.7.6 DataLink Data Recorder Via ReeferManager
NOTE
If the factory settings are used, you can skip this
section.
a. Refer to Section 3.19 for list of DataLink data record-
er setups.
b. Connect your computer to the download port of the
unit and start the ReeferManager program (refer to
Section 5.5 step c.). You will need ReeferManager
version 03.08.00
or higher.
NOTE
ReeferManager 03.08.00 is REQUIRED in or-
der to view, change and send new features to
and from the microprocessor.
c. In ReeferManager, go to the Serial Operations Tab,
and then click on Data Recorder/Microprocessor
setup button.
d. Select the Sensors to be recorded and whether you
wish averaged or snapshot recordings (averaged is
recommended for all temperature sensors; snap-
shot is recommended for voltage, amperage, &
RPM).
e. When the setup is correct, press the Send button to
send the new settings to the microprocessor.
f. From the “Confirm Send Information” Pop Up, check
the data you want to send and un-check the data you
don’t want to send. Click the OK button.
g. Verify that the settings were sent by waiting for the
confirmation pop up message.
NOTE
If the DataLink data recorder date and time
were not set earlier, they can be set from this
screen by clicking on Tools>Set Date and Time.
5.7.7 Microprocessor Final Checkout
a. Start the unit and allow it to run for a few minutes.
b. While the unit is running, scroll through the Data List
of the microprocessor. Verify that all the data is now
accurately displayed.
c. Initiate a Pretrip test. Allow the unit to complete the
Pretrip and check for any alarms. Make any neces-
sary repairs before returning the unit into service.