62-11389
7
−
99
Alarm
NO.
Steps
Alarm/Cause
Corrective Action
225
GENERAL MAINTENANCE DUE
•
TRIGGER–ON: The General Maintenance Hour Meter time has expired.
•
UNIT CONTROL: Alarm Only. Alarm Light will NOT be turned on.
•
RESET CONDITION: Alarm may be manually reset via keypad.
1
Check Unit Maintenance Records
Schedule unit into service facility for
maintenance.
Must be done soon!
2
Perform Maintenance
Perform appropriate engine & unit
maintenance.
Follow instructions on proper maintenance form.
3
Reset General Maintenance Hour Meter
a. Check that the General
Maintenance Hour Meter interval is
set for your requirements.
Reset configured Interval if required.
b. Reset General Maintenance Hour
Meter for the next service interval.
Hour Meter reset is a Functional Parameter.
Follow maintenance interval recommendations in
Section 8.2.
226
SERVICE SOON-PM #1 DUE
•
TRIGGER–ON: The Maintenance Hour Meter #1 time has expired.
•
UNIT CONTROL: Alarm Only. Alarm Light will NOT be turned on.
•
RESET CONDITION: Alarm may be manually reset via keypad.
1
Check Unit Maintenance Records
Schedule unit into service facility for
maintenance.
Must be done soon!
2
Perform Maintenance
Perform appropriate engine & unit
maintenance.
Follow instructions on proper maintenance form.
3
Reset Maintenance Hour Meter #1
a. Check that Maintenance Hour
Meter #1 interval is set for your
requirements.
Reset configured Interval if required.
b. Reset Maintenance Hour Meter #1
for the next service interval.
Hour Meter reset is a Functional Parameter.
Follow maintenance interval recommendations in
Section 8.2.