Alarm
NO.
Steps
Alarm/Cause
Corrective Action
60
DATALOGGER
(DataLink data recorder) TIME WRONG
•
TRIGGER–ON: The real time clock in the Data Recorder does not contain a valid date.
•
UNIT CONTROL: Engine and Standby Operation: alarm only.
•
RESET CONDITION: Auto Reset when the DataLink data recorder real time clock is reset, or alarm
may be manually reset by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
1
Check Real Time Cloc
k
Check Real Time Clock in the Data
List, or using ReeferManager.
Must show correct date and time. Change as needed
(Configuration List).
2
Reset Microprocessor
a. Place the Main Power switch in
the OFF position for 30 seconds and
then return it to the desired position.
Microprocessor powers up OK.
b. Check for valid Real Time Clock
reading in Data List.
Valid date and time in memory.
Alarm is cleared automatically.
c. Real Time Clock can not be
changed.
Replace microprocessor.
3
Microprocessor Defective
a. Download previous data using
Download PC Card, or
ReeferManager Program.
Data retrieval OK.
b. Replace microprocessor & set
Configurations, Functional
Parameters, Enter hours from
removed microprocessor, set
Maintenance Hour Meters, and
DataLink data recorder Setup.
New microprocessor in place.