Alarm
NO.
Steps
Alarm/Cause
Corrective Action
7.11 MICROPROCESSOR ALARMS
232
SETPOINT ERROR
•
TRIGGER–ON: There is an error in the set point that is stored in the microprocessor memory.
•
UNIT CONTROL: Unit Shutdown & Alarm.
•
RESET CONDITION: Auto Reset when a valid set point is entered, or alarm may be manually reset
by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
1
Check Set Point
a. Check set point setting.
Must be between -22 and +89.6
°
F (-30
°
and +32
°
C)
b. Enter new set point.
2
Reset Microprocessor
a. Place the Main Power switch in the
OFF position for 30 seconds, then
back to the desired position.
The microprocessor powers up OK and the latest set
point appears in the display.
b. Valid set point can not be entered
and alarm 232 remains active.
Download and replace microprocessor. Refer to
Section 5.7.
233
MODEL # ERROR
•
TRIGGER–ON: There is an error in the Model Number that is stored in the microprocessor memory
•
UNIT CONTROL: Unit Shutdown & Alarm
•
RESET CONDITION: Auto Reset only when a valid Model number is entered.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
1
Check Model Number
a. Check Model Number in
microprocessor.
b. Enter correct Model Number.
Check Model Number on Nameplate.
Select the correct model number in the “MODEL
NUMBER” Configuration. If correct model number is
not found, Install (or have Carrier Transicold dealer
install) latest software revision.
2
Reset Microprocessor
a. Place the Main Power switch in the
OFF position for 30 seconds, then
back to the desired position.
Microprocessor powers up OK.
b. Check for valid Model number in
Data List.
Valid number is present.
Alarm is cleared.
c. Valid model number can not be
entered and alarm remains active.
Download and replace microprocessor. Refer to
Section 5.7.