Table 5
−
2 Microprocessor Configurations - Continued
PRODUCTSHIELD ECONO
MIN TEMP
OFF
or
-20
°
F to +119.0
°
F
(-28.9
°
C to
+48.4
°
C
)
(in 0.5
°
incre-
ments)
Default:
119.0
°
F
(48.4
°
C )
OFF = There is no lower limit for this parameter.
Select the lowest ambient temperature desired to
activate ProductShield Econo.
If ProductShield Econo is Go To Continuous there
is a minimum 10
°
F range. Therefore, this parame-
ter’s upper limit is ProductShield Econo Maximum
Temperature minus 10
°
F (5.5
°
C).
PRODUCTSHIELD ECONO
MAX TEMP
OFF
or
-20
°
F to +119.0
°
F
(-28.9
°
C to
+48.4
°
C
)
(in 0.5
°
incre-
ments)
Default:
119.0
°
F
(48.4
°
C)
OFF = There is no upper limit for this parameter.
Select the highest ambient temperature desired to
activate ProductShield Econo
If ProductShield Econo Install is Go To Continuous
there is a minimum 10
°
F range. Therefore, this pa-
rameter’s lower limit is ProductShield Econo Min
Temp plus 10
°
F (5.5
°
C).
PRODUCTSHIELD
ECONO - DELTA-T
(used for “Go To S/S” only, not
available for “Go To Cont”)
OFF
+3.6
°
F to +27.0
°
F
(+2
°
C to 15
°
C) (in
0.5
°
increments
OFF = Delta-T is not used in determining when the
unit will go into Econo: Go To Start/Stop mode.
Select the desired delta-T value for activation of
ProductShield Econo. When Delta-T is below this
setting and within the minimum/maximum range, go
to start/stop will be allowed
PRODUCTSHIELD HIGH AIR
OFF
OFF = The unit will operate normally in high and
low speeds.
ON
ON = The unit will operate in high speed when the
ambient air temperature is
outside
a user defined
range. This provides increased air flow and good
product protection for extreme ambient temperat-
ures. Unit may return to low speed when ambient
comes back within the range.
HIGH AIR MIN. TEMP
OFF
OFF = There is no lower limit for this parameter.
-19
°
F to +119
°
F
(-28.3
°
C to
+48.3
°
C
)
in 0.5
°
F or
°
C
increments
Default:
119
°
F
(48.3
°
C )
Select the lower limit of the ambient range desired
for this parameter. Refer to Section 4.7.3 for more
information on High Air Min. Temp.
HIGH AIR MAX. TEMP
OFF
OFF = There is no upper limit for this parameter.
-19
°
F to +119
°
F
(-28.3
°
C to
+48.3
°
C
)
in 0.5
°
F or
°
C
increments
Default:
119
°
F
(48.3
°
C )
Select the upper limit of the ambient range desired
for this parameter. Refer to Section 4.7.3 for more
information on High Air Max. Temp.
HIGH AIR DELTA-T
OFF
OFF = Delta-T is not used for determining the activ-
ation/de-activation of High Air Delta-T
+3.6
°
F to +27.0
°
F
(+2
°
C to 15
°
C)
in 0.5
°
C or
°
F in-
crements
Select the desired Delta-T value for activation of
ProductShield High Air. Refer to Section 4.7.3 for
more information on High Air Delta-T.
PRODUCTSHIELD WINTER - XX
°
OFF
-20
°
F to +32.0
°
F
(-28.9
°
C to 0
°
C) (in
0.5
°
C or
°
F incre-
ments
Select the desired ambient temperature below
which ProductShield Winter will operate (forced
Continuous Run operation.)