62-11389
5
−
21
Table 5
−
2. Microprocessor Configurations - Continued
Configuration
Selections
Description
REMS1 (Remote Switch 1)
OR
REMS2 (Remote Switch 2)
NOTE
If the configuration is set for a
switch, not for a panel, the following
sub configuration will also be avail-
able.
NOT INSTALLED
DOOR OPEN
SWITCH OPEN
DOOR OPEN
SWITCH CLOSED
SWITCH ON
CONTACTS OPEN
SWITCH ON
CONTACTS
CLOSED
REMOTE PANEL
Switch not installed = There is no remote switch or
panel.
DOOR OPEN SWITCH OPEN = The remote switch
will be used as a door switch. The switch contacts
will be OPEN whenever the door is OPEN.
DOOR OPEN SWITCH CLOSED = The remote
switch will be used as a door switch. The switch
contacts will be CLOSED whenever the door is
OPEN.
SWITCH ON CONTACTS OPEN = The remote
switch will be used as a remote control switch. The
switch contacts will be OPEN whenever the switch
is in the ON position.
SWITCH ON CONTACTS CLOSED = The remote
switch will be used as a remote control switch. The
switch contacts will be CLOSED whenever the
switch is ON.
REMOTE PANEL = If set to this value, the remote
panel SYSTEM ON/OFF key will be enabled. The
switch panel mounted Main Power Switch must be
toggled out of the OFF position and the remote
panel SYSTEM ON/OFF key must be pressed for
the unit to operate. However, if the Override Re-
mote Switch 1 or 2 Functional Parameter is set to
YES, the remote panel is disabled.
•
REMS1
OR
•
REMS2
ALARM ONLY
UNIT SHUTDOWN
LOW ENGINE
SPEED
DATA RECORDER
ONLY
ALARM ONLY = When the switch is activated, a
warning alarm will be displayed in the Message-
Center.
UNIT SHUTDOWN = When the switch is activated,
a warning alarm will be displayed in the Message-
Center, and the unit will shutdown.
LOW ENGINE SPEED = When the switch is activ-
ated, the engine will be forced to low speed.
DATA RECORDER ONLY = The DataLink data re-
corder will record every time the the switch is activ-
ated. There will be no alarms or messages dis-
played in the MessageCenter.
SET TIME
Indicates to the microprocessor the time and date for the DataLink data
recorder Real Time Clock .
•
MONTH
1-12
Select the correct month of the year.
•
DAY
1-31
Select the correct day of the month.
•
YEAR
1998 - 2037
Select the correct year.
•
HOURS
0-23
Select the correct hour (0-11 is AM / 12-23 is PM)
•
MINUTES
0-59
Select the correct minute.