Fig. 6-33:
Selecting the "communication driver" "BR_WS"
5. Use the context menu of the driver that was just added to call the "Prop‐
erties" dialog.
Fig. 6-34:
Calling the "Properties" dialog of "BR_WS"
6. Make the following settings in the "Properties" dialog of "BR_WS":
●
"Serial encapsulation": "None"
●
"Timeout in ms": Enter a timer monitor for the communication con‐
nection. Recommended value for a communication connection to
the drive controller: ≥1000 ms.
●
"IP address": TCP/IP address of target control unit
●
"No connection check (CE)": "0" (the communication connection
should also be monitored in devices designated CE).
DOK-INDRV*-MLD3-**VRS*-AP02-EN-P
Bosch Rexroth AG
159/267
Rexroth IndraDrive Rexroth IndraMotion MLD (2G) as of MPx-18
Visualization and engineering interfaces