4-10
Protection and Control
BE1-951
Figure 4-7. Example 3 Using 79LO Logic to Modify Group Control
Setting Automatic Setting Group Control
Automatic setting group control settings are set at HMI screen 2.3 or through the communication ports
using the SP-GROUP command. Automatic setting group control settings are summarized in Table 4-4.
Table 4-4. Automatic Setting Group Control Settings
Setting
Range
Purpose
Default
sw_time
1 to 60
0 = disabled
Time in minutes that determines when a setting
change occurs once the sw_level setting is
exceeded.
0
sw_level
0 to 150
Percentage of the SG0 prot_ele setting that
must be exceeded for a setting group change to
occur.
0
ret_time
1 to 60
0 = disabled
Time in minutes that determines when a return
to SG0 will occur once the monitored current has
decreased below the ret_level setting.
0
ret_level
0 to 150
Percentage of the SG0 prot_ele setting that the
monitored current must decrease below in order
for a return to SG0.
0
prot_ele
51P, 51N, 151N,
51Q, 791, 792,
793, or 794
Determines when automatic setting group
changes occur. Time-Overcurrent elements 51P,
51N, or 51Q can be selected so that setting group
changes are based on load current. Recloser
Shots 791, 792, 793, or 794 can be used to switch
setting groups when the appropriate shot is
reached in a reclosing sequence. If one of the
recloser shots is entered as the prot_ele setting,
the sw_time, sw_level, ret_time, and ret_level
parameters are not required and should be
replaced with comma delimiters.
51P
Содержание BE1-951
Страница 157: ...BESTlogic Programmable Logic BE1 951 7 2 Figure 7 1 BESTlogic Function Blocks Courtesy of NationalSwitchgear com...
Страница 238: ...BE1 951 Human Machine Interface 10 5 Figure 10 5 Metering Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 239: ...10 6 Human Machine Interface BE1 951 Figure 10 6 Reports Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 270: ...12 2 Installation BE1 951 Figure 12 1 BE1 951 S1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 274: ...12 6 Installation BE1 951 Figure 12 5 BE1 951 H1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 283: ...BE1 951 Installation 12 15 Figure 12 16 Typical AC Connections Courtesy of NationalSwitchgear com...
Страница 394: ...A 18 Appendix BE1 951 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376 Courtesy of NationalSwitchgear com...
Страница 396: ...A 20 Appendix BE1 951 Figure A 16 Time Characteristic Curve G Long Inverse 99 1622 Courtesy of NationalSwitchgear com...
Страница 397: ...BE1 951 Appendix A 21 Figure A 17 46 Time Characteristic Curve Courtesy of NationalSwitchgear com...