67N Polarization:
Selectable any combination
Zero sequence Voltage (Requires 4W VT)
Zero Sequence Current (Requires IG)
Negative Sequence
Volts/HZ (24)
Pickup:
0.5 - 6V/Hz
Delay Time:
Inverse Squared Curve
T
D
M
T
T
=
-
(
)
1
2
T
T
= Time Trip
D
T
= Time Dial, Tip
M
Actual V Hz
Pickup V Hz
=
/
/
T
D X
ET
FST
X100
R
R
=
T
R
= Time to Reset
D
R
= Time Dial, Reset
ET = Elapsed Time
FST = Full Scale Trip Time (T
T
)
Directional Power (32, 132)
Mode:
Forward, Reverse
Pickup:
5A: 1 to 6,000 Watts, 3 Ph
1A: 1 to 1,200 Watts, 3 Ph
Time Delay:
0.05 to 600 seconds
Accuracy:
+3%
Sync-Check (25)
Delta Phase Angle:
1 - 45 degrees
Delta Voltage Magnitude:
1 - 20 V
Delta Frequency:
0.01 - 0.50 Hz
Sync-Check, Voltage Monitor (25VM)
Live voltage threshold
10 - 150 V
Dead voltage threshold
10 - 150 V
Dropout Time delay
0.050 - 60 seconds
Logic:
Dead Phase/Dead Aux.
Dead Phase/ Live Aux.
Live Phase/ Dead Aux.
Two independent outputs:
25VM1 and 25VM2
Phase Undervoltage Function (27P)
Pickup
Setting Range:
10 to 300 V
Setting Increment:
0.1 V (for a range of 0 - 99.9)
1.0 V (for a range of 100 - 150)
Pickup Accuracy:
±2% or 1 V
Dropout/Pickup Ratio:
102%
Time Delay
Setting Range:
0.050 to 600 seconds
Increment:
1 millisecond from 0 to 999 milliseconds
0.1 second from 1.0 to 9.9 seconds
1 second from 10 to 600 seconds
Accuracy:
±0.5% or ±1 cycle whichever is greater
Содержание BE1-951
Страница 157: ...BESTlogic Programmable Logic BE1 951 7 2 Figure 7 1 BESTlogic Function Blocks Courtesy of NationalSwitchgear com...
Страница 238: ...BE1 951 Human Machine Interface 10 5 Figure 10 5 Metering Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 239: ...10 6 Human Machine Interface BE1 951 Figure 10 6 Reports Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 270: ...12 2 Installation BE1 951 Figure 12 1 BE1 951 S1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 274: ...12 6 Installation BE1 951 Figure 12 5 BE1 951 H1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 283: ...BE1 951 Installation 12 15 Figure 12 16 Typical AC Connections Courtesy of NationalSwitchgear com...
Страница 394: ...A 18 Appendix BE1 951 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376 Courtesy of NationalSwitchgear com...
Страница 396: ...A 20 Appendix BE1 951 Figure A 16 Time Characteristic Curve G Long Inverse 99 1622 Courtesy of NationalSwitchgear com...
Страница 397: ...BE1 951 Appendix A 21 Figure A 17 46 Time Characteristic Curve Courtesy of NationalSwitchgear com...