B-5
Table B-10. User Programmable Name Setting Command
ASCII Command
Function
HMI Screen
SN[-<var>[=<name>,<TRUE label>,<FALSE label>]]
Read/Set user programmable names.
N/A
Table B-11. Protection Setting Commands
ASCII Command
Function
HMI Screen
S<g>
Read all protection settings.
N/A
S<g>-24[=<Pickup)>,<Time Delay>,<Reset Time
Delay>]
Read/Set 24 pickup level, time delay and
reset delay
5.x.1.1
S<g>-25[=<volts>,<ang>,<slip>,<mode>]
Read/Set 25 delta volts, phase angle, slip
frequency and mode
5.x.2.1
S<g>-27<x>[=<Pickup>,<Time Delay>]
Read/Set 27 pickup level, time delay, and
mode.
5.x.3.1
S<g>-27R[=<Pickup>,<mode>]
Read/Set (51)/27R control level and
operating mode.
5.x.7.5
S<g>-32[=<Mode>,<BLK logic>]
Read/Set Logic for 32 Function Modules
5.x.4.1
S<g>-47[=<Pickup>,<Time Delay>]
Read/Set 47 pickup level and time delay.
5.x.5.1
S<g>-<x>50T<p>[=<Pickup>,<Time Delay>]
Read/Set 50TP/50TN pickup level and
time delay.
5.x.6.1 to
5.x.6.6
S<g>-51<p>[=<Pickup>,<Time Delay>,<Curve>]
Read/Set 51P/51N pickup level, time
delay, and curve.
5.x.7.1 to
5.x.7.4
S<g>-<x>59<p>[=<Pickup>,<Time Delay>]
Read/Set 59 pickup level, time delay, and
mode.
5.x.8.1
5.x.8.2
S<g>-<x>62[=<T1>,<T2>]
Read/Set 62 time delay.
5.x.9.1
S<g>-67N[=<Mode>,<Quantity>]
Read/Set 67 Neutral Polarizing Mode and
Quantities
5.x.10.1 and
5.x.10.2
S<g>-79<x>[=<Time Delay>]
Read/Set 79 time delay
5.x.11.1 to
5.x.11.4
S<g>-79SCB[=<step list>]
Read/Set 79 Sequence Controlled Block
output
5.x.11.5
S<g>-<x>81[=<Pickup>,<Time Delay>,<mode>]
Read/Set 81 pickup level, time delay, and
mode.
5.x.12.1 to
5.x.12.6
S<g>-81INH[=<Pickup>]
Read/Set 81 undervoltage inhibit level.
5.x.12.7
SP-60FL[=<I_Blk>,<V_Blk>]
Read/Set loss of potential pickup setting.
5.5.2.1
5.5.2.2
SP-BF[=<time>[m/s/c]]
Read/Set the breaker failure timer setting
5.5.1.1
SP-CURVE[=<A>,<B>,<C>,<N>,<R>]
Read/Set the user programmable 51
curve parameters.
N/A
Table B-12. Global Command
ASCII Command
Function
HMI Screen
GS-PW<t>[=<password>,<com ports(0/1/2)>]]
Read or change a password.
N/A
Содержание BE1-951
Страница 157: ...BESTlogic Programmable Logic BE1 951 7 2 Figure 7 1 BESTlogic Function Blocks Courtesy of NationalSwitchgear com...
Страница 238: ...BE1 951 Human Machine Interface 10 5 Figure 10 5 Metering Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 239: ...10 6 Human Machine Interface BE1 951 Figure 10 6 Reports Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 270: ...12 2 Installation BE1 951 Figure 12 1 BE1 951 S1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 274: ...12 6 Installation BE1 951 Figure 12 5 BE1 951 H1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 283: ...BE1 951 Installation 12 15 Figure 12 16 Typical AC Connections Courtesy of NationalSwitchgear com...
Страница 394: ...A 18 Appendix BE1 951 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376 Courtesy of NationalSwitchgear com...
Страница 396: ...A 20 Appendix BE1 951 Figure A 16 Time Characteristic Curve G Long Inverse 99 1622 Courtesy of NationalSwitchgear com...
Страница 397: ...BE1 951 Appendix A 21 Figure A 17 46 Time Characteristic Curve Courtesy of NationalSwitchgear com...