background image

MPD-192

Motor Protection Device

Over/Under Current 

Over/Under Frequency

Over/Under Voltage

Single Phase Prevention

Short Circuit

Unbalance

Phase Loss

Lock Rotor Point
Phase Sequence

Neutral Loss

User Selectable Trip Time

Auto/Manual Reset Function

True RMS Measurement

INPUT:

Voltage AC

Direct Voltage AC

30 to 300V(L - N)
50 to 500V(L - L)

Burden

Voltage AC

Current AC

Burden

Primary CT Ratio

Secondary Current AC

Overload

Frequency

 Up  to 6A continuous

45.0 to 65.0 Hz

DIMENSION:

Size (mm)

Panel Cutout (mm)

96 (H) X 96 (W) X 52 (D) mm

92 (H) X 92 (W) mm

FEATURES

Protection Available

TECHNICAL SPECIFICATION

< 0.2VA

5 to 6000 Amp selectable 

< 0.2VA

60mA to 5 Amp 

NETWORK SELECTION:

3 Phase - 4 Wire,3 Phase - 3 Wire

DISPLAY AND KEYS:

Display

3 Digit, 3 Line 7 Seg 0.56”,
RED LED

Keys

SET, INC, DEC, ACK

Page 1

TERMINAL CONNECTION

Supply Voltage

100 to 270V AC, 50Hz

Power Consuption

4VA @ 230 AC MAX

AUXILIARY SUPPLY:

OUTPUT SPECIFICATION:

Relay

2 Nos

Relay Type

st

1  Relay ( NO - C - NC )

nd 

2 Relay ( NO - C )

Rating 

st

1  Relay 10Amp, 250V AC 

nd 

2 Relay 5 Amp, 250V AC 

TIME PARAMETER:

Power On Delay

0 to 99 Sec

Initial Time Delay

0 to 99 Sec

Trip Delay Time

0 to 999 Sec

(Voltage, Current, Frequency, 
SSP, Unbalance)
Scrolling Time

1 to 99 Sec

Reset Time

0 to 99 Sec

TRIP SETTING:

Under Current

0.00 to CTR

0.00 to CTR

Over Current

Under Voltage

50 to 520V For 3Ø - 3W
30 to 300V For 3Ø - 4W

Over Voltage

50 to 550V For 3Ø - 3W
30 to 330V For 3Ø - 4W

Over / Under Frequency

45.0 to 65.0 Hz

Lock Rotor Point

0.5 to 9.0 Scale

Short Circut

1 - 9 Scale 

Unbalance

5 - 60%

ENVIRONMENTAL CONDITION:

Working Temperature  

Storage Temperature   
Relative Humidity   

0 to 55°C
0 to 55°C

95 % RH Non-Condensing

IP-65 (Front side As per
IS/IEC 60529 : 2001)

Protection Level
(As Per request)

NC

C

NO

Relay-1

1

2

3

4

7

8

9

12

13

14

10

11

5

16

17

18

19

20

6

15

S1

S1

S1

S2

S2

S2

R

Y

B

Accuracy Class: 1.0

System:
                          

3Ph-4W/3Ph-3W

Relay-2

V

R

V

Y

V

B

N

L

N

!

Made in India

www.multispanindia.com

NO

C

100  
270V AC
    

50Hz,4VA

CAT III

Range:

Current: 
     60mA To 5.00A AC               

Voltage 
      (P-P) : 50-520V AC

(P-N) : 30-300V AC

CT Primary: 5A to 6000A

  

Class 1.0 (Standard)

ACCURACY

Содержание MPD-192

Страница 1: ...ay Type st 1 Relay NO C NC nd 2 Relay NO C Rating st 1 Relay 10Amp 250V AC nd 2 Relay 5 Amp 250V AC TIME PARAMETER Power On Delay 0 to 99 Sec Initial Time Delay 0 to 99 Sec Trip Delay Time 0 to 999 Se...

Страница 2: ...age of ventilating parts 2 Clean the equipment with a clean soft cloth Do not use isopropyl alcohol or any other cleaning agent 3 Fusible resistor must not be replaced by operator Read complete instru...

Страница 3: ...hase loss 3 B Phase loss Phase Loss P H A R L O S P H A Y L O S P H A B L O S Phase Sequence Message Phase Fault P H A S E Q F L T Sequence FAULT MASSAGE R Under Frequency Fault Message Under frequenc...

Страница 4: ...Q 5 0 0 H Z R Fault L1 L2 L3 VLL VLN A KA r U N C 2 8 7 R Fault L1 L2 L3 VLL VLN A KA 1 2 0 1 2 0 1 2 0 3 3 W NETWORK CONNECTION 3 3W 3 4W NETWORK CONNECTION NC C NO Relay 1 1 2 3 4 7 8 9 12 13 14 10...

Страница 5: ...Frequency Enable Disable O F 5 5 0 V A L Over Frequency 45 0 to 65 0Hz Value O f 5 T I M Over Frequency 0 to 999 sec Value If Enable If Disable Press Key SET Press Key SET Press Key SET Press Key SET...

Страница 6: ...ET Press Key SET Press Key SET Press Key SET Press Key SET Press Key SET Press Key SET Press Key SET If Enable If Disable If Enable If Disable If Enable If Disable Enter Password 29 P A S 2 9 Enter Pa...

Страница 7: ...y will turn off when fault is achieved otherwise Relay will remain turn on 2 If Relay fault selected is on then Relay will turn on when fault is achieved otherwise Relay will remain turn off Power On...

Страница 8: ...1 0A Y Phase Power ON Under Current Delay Under Current Delay R B Phase CONTROL FUNCTION Lock Rotor Point Power On 5 Sec Intial Time Delay 5 Sec Lock Rotor Point Enable Over Current Value 2 0A Relay F...

Отзывы: