Output
Purpose
Output Description
Variable
Label
State Labels
TRUE (1)
FALSE (0)
BE1-951
Application
8-45
VO8
Time-Overcurrent Trip TRUE when any time overcurrent
element trips.
51_TRIP
TRIP
NORMAL
BESTlogic Expression: VO8 = 51PT+51NT+51QT
VO9
Instantaneous
Overcurrent Trip.
TRUE when any instantaneous
overcurrent element trips.
50_TRIP
TRIP
NORMAL
BESTlogic Expression: VO9 = 50TPT+50TNT+50TQT
VO10
Breaker Failure
Initiate.
Initiate breaker failure timing when
protective trip expression is TRUE
or when external initiate contact is
sensed and any of the fault
detectors is picked up.
SUPV-BFI
BFI-INI
NORMAL
BESTlogic Expression: VO10 = VO11+IN3*IN3*150TQPU
VO11
Protective Trip
Expression.
TRUE when any 50 or 51 element
has timed out.
PROT_TRIP
TRIP
NORMAL
BESTlogic Expression: VO11 = 50TPT+50TNT+50TQT+51PT+51NT+51QT
VO12
Protection Picked Up
Expression.
TRUE when any 50 or 51 element
has picked up.
PROT_PU
PU
NORMAL
BESTlogic Expression: VO12 = 51PPU +51NPU+51QPU
VO13
Alarm Mask 21.
VO13
TRUE
FALSE
BESTlogic Expression: VO13 = 0
VO14
Alarm Mask 22.
VO14
TRUE
FALSE
BESTlogic Expression: VO14 = 0
VO15
Alarm Mask 23.
Indicates that the relay is in Test
mode and that breaker failure is
disabled. TRUE if IN4 is de-
energized or if virtual switch 343 is
closed.
TEST_MODE
TEST
NORMAL
BESTlogic Expression: VO15 = /IN4+343
Содержание BE1-951
Страница 157: ...BESTlogic Programmable Logic BE1 951 7 2 Figure 7 1 BESTlogic Function Blocks Courtesy of NationalSwitchgear com...
Страница 238: ...BE1 951 Human Machine Interface 10 5 Figure 10 5 Metering Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 239: ...10 6 Human Machine Interface BE1 951 Figure 10 6 Reports Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 270: ...12 2 Installation BE1 951 Figure 12 1 BE1 951 S1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 274: ...12 6 Installation BE1 951 Figure 12 5 BE1 951 H1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 283: ...BE1 951 Installation 12 15 Figure 12 16 Typical AC Connections Courtesy of NationalSwitchgear com...
Страница 394: ...A 18 Appendix BE1 951 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376 Courtesy of NationalSwitchgear com...
Страница 396: ...A 20 Appendix BE1 951 Figure A 16 Time Characteristic Curve G Long Inverse 99 1622 Courtesy of NationalSwitchgear com...
Страница 397: ...BE1 951 Appendix A 21 Figure A 17 46 Time Characteristic Curve Courtesy of NationalSwitchgear com...