BE1-951 ASCII
Command
Interface
11-5
EXIT Command Example
Release programming privileges and save settings changes.
>EXIT<CR>
SAVE CHANGES (Y/N/C)?
Prompt to save Yes, No, or Continue
>Y<CR>
Confirmation to save changes
CHANGES SAVED
Confirmation that changes were saved
Reading All Settings
All user programmable settings can be listed using the S command. This read-only command is useful for
documenting relay status during installation. The settings retrieved by the S command can be saved to a
standard text file and sent to another relay to be configured with the same settings. This type of settings
transfer takes less than one minute.
S Command
Purpose:
Read all relay setting parameters.
Syntax:
S
The S command returns the values of relay setting parameters in the same form that they are programmed.
It can be used at the end of a programming session to make a record of the relay settings. If saved in a file,
the report can be sent to another BE1-951 that will use the same settings. Because the report that is created
is a set of commands, sending the report to a different relay re-programs that relay with the settings
contained in the S report.
Reading Specific Groups of Settings
While the S command is useful for reading all relay settings, several commands are available to read specific
groups of settings.
Note: In examples throughout this manual, relay responses are printed in
Courier
typeface.
SA Command
Purpose:
Read all alarm settings for Major and Minor alarms.
Syntax:
SA
SA Command Example
1.
Read all alarm settings.
>SA
SA-BKR1=0,0; SA-BKR2=0,0; SA-BKR3=0,0
SA-DIP=0.00; SA-DIN=0.00; SA-DIQ=0.00
SA-DVAR= 0.00KVAR
SA-DWATT= 0.00KW
SA-LGC=0
SA-MAJ=0
SA-MIN=0
SA-RESET=0
SB Command
Purpose:
Read all breaker settings.
Syntax:
SB
SB Command Example
1.
Read all breaker settings.
>SB
SB-DUTY=0,0.000e+00
SB-LOGIC=/IN1
Содержание BE1-951
Страница 157: ...BESTlogic Programmable Logic BE1 951 7 2 Figure 7 1 BESTlogic Function Blocks Courtesy of NationalSwitchgear com...
Страница 238: ...BE1 951 Human Machine Interface 10 5 Figure 10 5 Metering Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 239: ...10 6 Human Machine Interface BE1 951 Figure 10 6 Reports Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 270: ...12 2 Installation BE1 951 Figure 12 1 BE1 951 S1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 274: ...12 6 Installation BE1 951 Figure 12 5 BE1 951 H1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 283: ...BE1 951 Installation 12 15 Figure 12 16 Typical AC Connections Courtesy of NationalSwitchgear com...
Страница 394: ...A 18 Appendix BE1 951 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376 Courtesy of NationalSwitchgear com...
Страница 396: ...A 20 Appendix BE1 951 Figure A 16 Time Characteristic Curve G Long Inverse 99 1622 Courtesy of NationalSwitchgear com...
Страница 397: ...BE1 951 Appendix A 21 Figure A 17 46 Time Characteristic Curve Courtesy of NationalSwitchgear com...