11-8
ASCII Command Interface
BE1-951
SL-162:0,0,0
SL-79:0,0,0,0,0
SL-BF:1,VO10,VO15
SL-GROUP:2,/IN2,0,0,0,0
SL-43:0
SL-143:0
SL-243:0
SL-343:2
SL-101:1
SL-VOA:0
SL-VO1:BFPU+VO8+101T
SL-VO2:101C
SL-VO3:/IN2
SL-VO4:VO9
SL-VO5:BFT
SL-VO6:0
SL-VO7:0
SL-VO8:51PT+51NT+51QT
SL-VO9:50TPT+50TNT+50TQT
SL-VO10:VO11+150TPPU*IN3+150TNPU*IN3+150TQPU*IN3
SL-VO11:50TPT+50TNT+50TQT+51PT+51NT+51QT
SL-VO12:51PPU+51NPU+51QPU
SL-VO13:0
SL-VO14:0
SL-VO15:343+/IN4
>
Configuring the Serial Port Communication Protocol
The serial communication protocol is defined with the SG-COM command shown below.
SG-COM Command
Purpose:
Read or change the serial communications protocol.
Syntax:
SG-COM<#> [= <baud>,<Ax>,<Px>,<Rx>,<,Xx>,<MFx>,<MPx>, <MRx>,<MSx>]
Comments:
Password Access Privilege G or Privilege S required to change settings
#
= port number. (0 = Front, 1 = Rear 232, 2= Rear 485)
baud = baud rate (300/600/1200/2400/4800/9600/19K)
Ax
= Address for polled operation where x = 0 (No polling) to 65534
Px
= Page length (lines/pg) setting where x = 0 (No page mode) to 40
Rx
= Reply acknowledgment level where x = 0 (disabled), or 1 (enabled)
Xx
= Xon/Xoff setting where X0 = handshake disabled, X1 = handshake enabled.
The following parameters pertain to relays using Modbus
TM
communication
protocol at COM2.
MFx = Modbus
TM
extended precision format where x = 0 for floating point or 1 for triple
precision
MPx = Modbus
TM
parity where x = N(None), O(Odd), and E(Even).
MRx = Modbus
TM
remote delay time where x = 10(msec.) to 200(msec.).
MSx = Modbus
TM
stop bit where x = 1 for one stop bit or 2 for two stop bits.
If a non-zero address is programmed in the 'A' parameter, then the relay will ignore all commands that are
not preceded by its specific address. If an address of 0 is programmed, then the relay will respond with an
error message for any command preceded by an address.
If polling software sends a command preceded by an address of 0, then that command will be treated as a
global command. All relays will execute the command but no relay will respond to avoid bus contention.
NOTE: Polling is disabled on COM0 (Front RS-232), so an attempt to program an address other than A0
will cause an error message. The factory default settings are 9600,A0,P24,R1,X1 for COM0 and COM1 and
9600, A0,P0,R1,X0 for COM2.
Содержание BE1-951
Страница 157: ...BESTlogic Programmable Logic BE1 951 7 2 Figure 7 1 BESTlogic Function Blocks Courtesy of NationalSwitchgear com...
Страница 238: ...BE1 951 Human Machine Interface 10 5 Figure 10 5 Metering Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 239: ...10 6 Human Machine Interface BE1 951 Figure 10 6 Reports Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 270: ...12 2 Installation BE1 951 Figure 12 1 BE1 951 S1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 274: ...12 6 Installation BE1 951 Figure 12 5 BE1 951 H1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 283: ...BE1 951 Installation 12 15 Figure 12 16 Typical AC Connections Courtesy of NationalSwitchgear com...
Страница 394: ...A 18 Appendix BE1 951 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376 Courtesy of NationalSwitchgear com...
Страница 396: ...A 20 Appendix BE1 951 Figure A 16 Time Characteristic Curve G Long Inverse 99 1622 Courtesy of NationalSwitchgear com...
Страница 397: ...BE1 951 Appendix A 21 Figure A 17 46 Time Characteristic Curve Courtesy of NationalSwitchgear com...