13-54
Testing and Maintenance
BE1-951
Command
Purpose
Y
Confirm overwrite
SL-N=MODE3
Sets MODE3 as custom logic name
SL-243=3
Sets 243 switch for Mode 3 operation
SL-VO1=243
Enables OUT1 to close for 243
EXIT;Y
Exit and save settings.
Step 2 Prepare to monitor the virtual switch operation. An ohmmeter or continuity tester may be used to
monitor the contact status of OUT1.
Step 3
Transmit the commands in Table 13-83 to the relay. These commands pulse the 243 switch on and
off once.
Result: OUT1 contact closes for 200 milliseconds and returns to the open state.
Table 13-83. x43 Mode 3 Pulse Commands
Command
Purpose
A=
Gain write access
CS-243=P
Selects 243 for On operation
CO-243=1
Executes 243 for On operation
Virtual Breaker Control Switch
Purpose: To verify 101 virtual breaker control switch operation.
Reference Commands: SL-101, CS/CO-101C, CS/CO-101T
Step 1 Prepare the 101 virtual breaker control switch for testing by transmitting the commands in Table
13-84 to the relay.
Table 13-84. 101 Virtual Breaker Control Switch Test Commands
Command
Purpose
A=
Gain write access
SL-N=NONE
Zero out custom logic settings. Overwrite with logic=none settings.
Y
Confirm overwrite
SL-N=S101
Sets S101 as custom logic name
SL-101=1
Enables 101 switch
SL-VO1=101T
Enables OUT1 to close when 101T is TRUE
SL-VO1=101C
Enables OUT2 to close when 101C is TRUE
SL-VO1=101SC
Enables OUT3 to close when 101SC is TRUE
EXIT;Y
Exit and save settings.
Содержание BE1-951
Страница 157: ...BESTlogic Programmable Logic BE1 951 7 2 Figure 7 1 BESTlogic Function Blocks Courtesy of NationalSwitchgear com...
Страница 238: ...BE1 951 Human Machine Interface 10 5 Figure 10 5 Metering Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 239: ...10 6 Human Machine Interface BE1 951 Figure 10 6 Reports Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 270: ...12 2 Installation BE1 951 Figure 12 1 BE1 951 S1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 274: ...12 6 Installation BE1 951 Figure 12 5 BE1 951 H1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 283: ...BE1 951 Installation 12 15 Figure 12 16 Typical AC Connections Courtesy of NationalSwitchgear com...
Страница 394: ...A 18 Appendix BE1 951 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376 Courtesy of NationalSwitchgear com...
Страница 396: ...A 20 Appendix BE1 951 Figure A 16 Time Characteristic Curve G Long Inverse 99 1622 Courtesy of NationalSwitchgear com...
Страница 397: ...BE1 951 Appendix A 21 Figure A 17 46 Time Characteristic Curve Courtesy of NationalSwitchgear com...