BE1-951
Testing and Maintenance
13-51
Table 13-74. BF Time Delay Commands
Command
Purpose
A=
Gain write access
SP-BF=100m
Set BF time delay at 100 milliseconds
EXIT;Y
Exit and save settings
Step 5 Verify the BF time delay by applying the pickup current obtained in Step 3 for the duration given
in the following steps.
A. Apply pickup current to phase A for 4 cycles (67 ms at 60 Hz). No trip should occur.
B. Apply pickup current to phase A for 5 cycles. (83 ms at 60 Hz). No trip should occur.
C. Apply pickup current to phase A for 7 cycles (117 ms at 60 Hz). A BF trip should occur. Use
the RS-LGC command to retrieve an SER report and verify that a BF trip was logged 100
millis5 percent (+11/4, -1/4) after application of pickup current.
Step 6 (Optional) De-energize relay input IN3. This will block the breaker fail logic and cause OUT1 and
OUT2 to open. Verify that relay outputs OUT1 and OUT2 remain open (BF element does not
operate) even though pickup current is applied. De-energize IN3 and verify that OUT2 (and
subsequently OUT1) closes. Remove current from phase A.
Step 7 (Optional) Apply pickup current to phase A. OUT2 and OUT1 should close. De-energize IN4 and
verify that OUT1 and OUT2 open. Remove current from phase A.
Step 8 Energize IN4 and apply 0.7 A of current to the phase A current input and measure the time
between the application of current and OUT1 closing. OUT2 should have closed immediately when
current was applied. Verify that the BF timer operated within the specified accuracy of +5 percent
or +11/4, -1/4 cycles, whichever is greater.
Step 9 (Optional) Repeat Steps 3 through 8 for the phase B and phase C elements.
Virtual Switches
Purpose: To verify operation of the 43/143/243/343 virtual switches.
Reference Commands: SL-43/143/243/343, CS/CO-43/143/243/343
To test virtual switches, we verify each mode of operation but do not verify each of the four virtual switches.
In your testing, you may substitute any or all of the switches as desired. If you give an invalid command such
as CS-243=1/CO-243=1 when switch 243 is programmed for mode 3 operation, the relay will reject the
command and return an INVALID PARAMETER message through the ASCII command interface. For more
information about virtual switch operation, see Section 4,
Protection and Control, Virtual Switches. You may
verify operation of virtual switches by monitoring the programmed output contacts, HMI screen 1.5.4, or by
using the RS-LGC command to retrieve logic variable data from the SER. You also may use the RG-STAT
command. See Section 6,
Reporting and Alarm Functions for more information about reports.
Mode 1 - On/Off/Pulse
Step 1 Prepare the x43 virtual switch for Mode 1 testing by transmitting the commands in Table 13-75
.
Table 13-75. x43 Mode 1 Test Commands
Command
Purpose
A=
Gain write access
SL-N=NONE
Zero out custom logic settings. Overwrite with
logic=none settings.
Y
Confirm overwrite
SL-N=MODE1
Sets MODE1 as custom logic name
SL-43=1
Sets 43 for Mode 1 operation
Содержание BE1-951
Страница 157: ...BESTlogic Programmable Logic BE1 951 7 2 Figure 7 1 BESTlogic Function Blocks Courtesy of NationalSwitchgear com...
Страница 238: ...BE1 951 Human Machine Interface 10 5 Figure 10 5 Metering Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 239: ...10 6 Human Machine Interface BE1 951 Figure 10 6 Reports Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 270: ...12 2 Installation BE1 951 Figure 12 1 BE1 951 S1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 274: ...12 6 Installation BE1 951 Figure 12 5 BE1 951 H1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 283: ...BE1 951 Installation 12 15 Figure 12 16 Typical AC Connections Courtesy of NationalSwitchgear com...
Страница 394: ...A 18 Appendix BE1 951 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376 Courtesy of NationalSwitchgear com...
Страница 396: ...A 20 Appendix BE1 951 Figure A 16 Time Characteristic Curve G Long Inverse 99 1622 Courtesy of NationalSwitchgear com...
Страница 397: ...BE1 951 Appendix A 21 Figure A 17 46 Time Characteristic Curve Courtesy of NationalSwitchgear com...