12-30
Installation
BE1-951
SETTINGS
Settings for your application need to be entered and confirmed before placing the relay in service. Register
settings such as breaker operations and breaker duty can be entered to match the current state of your
system.
PREPARING THE RELAY FOR SERVICE
Basler microprocessor-based protection systems are similar in nature to a panel of electromechanical or
solid-state component relays. Both must be wired together with inputs and outputs, and have operating
settings applied. Logic settings determine which protection elements are electronically wired to the inputs
and outputs of the device. Operating settings determine the pickup thresholds and time delays.
The logic and operating settings should be tested by applying actual inputs and operating quantities and
verifying proper output response. For more details, refer to Section 14,
Testing and Maintenance. All of the
following connections and functions should be verified during commissioning tests.
•
Proper connection and sensing of current and voltage signals
•
Input and output contact connections
•
I/O sensing versus virtual sensing
•
Settings validation
•
Proper operation of equipment (main or auxiliary)
•
Proper alarming (to SCADA) and/or targeting
Refer to Section 7,
BESTlogic Programmable Logic for information about customizing preprogrammed logic
and creating user-defined logic, and Section 8,
Application for information about the application of
preprogrammed logic schemes.
COMMUNICATIONS CONNECTIONS
The following paragraphs describe the communication connections for the BE1-951. Section 11,
ASCII
Command Interface provides information about using the relay communication interface and lists all
communication commands along with a description and the syntax for each command.
RS-232 Connectors
Front and rear panel RS-232 connectors are Data Communication Equipment (DCE) DB-9 female
connectors. Connector pin numbers, functions, names and signal directions are shown in Table 12-1.
RS-232 cable connection diagrams are provided in Figures 12-33 through 12-35. Optional Clear to Send
(CTS) and Request to Send (RTS) connections are required only if hardware handshaking is enabled.
Table 12-1. RS-232 Pinouts (COM0 and COM1)
Pin
Function
Name
Direction
1
Shield
----
N/A
2
Transmit Data
TXD
From Relay
3
Receive Data
RXD
Into Relay
4
N/C
----
N/A
5
Signal Ground
GND
N/A
6
N/C
----
N/A
7
N/C
----
N/A
8
N/C
----
N/A
9
N/C
----
N/A
Содержание BE1-951
Страница 157: ...BESTlogic Programmable Logic BE1 951 7 2 Figure 7 1 BESTlogic Function Blocks Courtesy of NationalSwitchgear com...
Страница 238: ...BE1 951 Human Machine Interface 10 5 Figure 10 5 Metering Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 239: ...10 6 Human Machine Interface BE1 951 Figure 10 6 Reports Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 270: ...12 2 Installation BE1 951 Figure 12 1 BE1 951 S1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 274: ...12 6 Installation BE1 951 Figure 12 5 BE1 951 H1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 283: ...BE1 951 Installation 12 15 Figure 12 16 Typical AC Connections Courtesy of NationalSwitchgear com...
Страница 394: ...A 18 Appendix BE1 951 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376 Courtesy of NationalSwitchgear com...
Страница 396: ...A 20 Appendix BE1 951 Figure A 16 Time Characteristic Curve G Long Inverse 99 1622 Courtesy of NationalSwitchgear com...
Страница 397: ...BE1 951 Appendix A 21 Figure A 17 46 Time Characteristic Curve Courtesy of NationalSwitchgear com...